Large-scale experimental study of interaction between fallout of tempered glass façade and enclosure fire dynamics
Abstract
Abstract This work presents several large-scale experiments on the interaction between fallout of tempered glass façade and enclosure fire dynamics. The experimental setup consisted of a compartment (1.8 × 1.4 × 1.4 m 3 ) with a fixed glass frame on one side to install a glass façade, which can contain 4 pieces of 660 × 630 mm 2 single-layer tempered glass at most. Some experiments were designed to investigate the influence of different glass positions on the framework on the breakage time, surface temperature, and heat flux. The flashover in all tests occurred before tempered glass breakage. Generally, the upper-installed glasses may lead to an earlier flashover but increase the breaking time. The first breakage normally occurred on the upper layer. The analysis indicated that with the lower opening on the framework, the critical time of flashover was 230 s, and the breakage occurred at 242 s. With the upper opening on the framework, the critical time of flashover was 148 s, but the breakage occurred at 296 s. Meanwhile, the maximum temperature differences between the central and shaded areas exceeded 150 ℃ in all cases, resulting in tempered glass breakage and fallout. The critical total heat flux was 88 kW/m 2 but the radiative heat flux accounted for only 12.5% of the total heat flux before breakage.
BibTeX
@article{haodong2024large,
author = {Chen Haodong and Yinghui Wang},
title = {{Large-scale experimental study of interaction between fallout of tempered glass façade and enclosure fire dynamics}},
journal = {Journal of Physics Conference Series},
year = {2024},
doi = {10.1088/1742-6596/2885/1/012059},
}Ask Althea to put this paper to the test.
Loading related content...