Investigation on the Ampacity of AC Submarine Cables in J-Type Conduit Trenchless Installation

Xunping Yan, Yun Cong, Gang Qian, Jianliang Xu, Lu Sun, Zhen LiuEnergies 2025 · DOI

TL;DR

This paper investigates how J-type conduit trenchless installation affects the current-carrying capacity (ampacity) of AC submarine cables. Using a sophisticated finite element model, the researchers found that burial depth, the material of the conduit, and the surrounding environmental temperature significantly impact how much current a cable can safely handle, with implications for designing more efficient and reliable subsea power transmission systems.

What Problem Does This Paper Address?

As offshore wind farms and trans-sea transmission projects expand, submarine cables are crucial. However, in areas with challenging terrain or where excavation is prohibited (like seawalls), traditional burial methods are difficult. The J-type conduit trenchless installation offers a solution, guiding cables through a pre-installed conduit. The challenge is that this installation method creates a complex thermal environment around the cable. Unlike cables buried directly in the seabed, J-type conduits introduce internal media (like air, seawater, or mud) and conduit materials that can impede heat dissipation. This reduced ability to shed heat limits the cable's ampacity, potentially becoming a bottleneck for power transmission efficiency and requiring careful consideration during design and operation. This paper aims to quantify these effects and understand how different factors influence the ampacity in these J-type conduit systems.

Methods

The researchers employed a coupled electromagnetic-thermal-fluid finite element model (FEM) using COMSOL 6.1. This multi-physics approach allowed them to simulate the complex interactions within the J-type conduit system.

  • Electromagnetic Module: This module calculated Joule heating in the conductors and induction heating in the cable's metallic layers.
  • Thermal Transfer Module: This module simulated heat conduction and convection within the cable, the conduit's internal medium, the conduit material itself, and the surrounding soil.
  • Fluid Flow Module: This module modeled the behavior of the internal fluid media (air, seawater, muddy water) under laminar flow conditions.

The model was validated against the IEC-60287 standard, showing a good agreement with an average error of 4.9%. The study systematically varied parameters like burial depth (2.0m, 2.5m, 3.0m), internal media (air, seawater, muddy water, and mixtures), conduit materials (PE, PVC, copper, stainless steel), and environmental temperatures (10°C, 20°C, 30°C) to assess their impact on cable ampacity.

Datasets

Not discussed in the paper. The study relies on a numerical model and simulated parameters based on typical materials and conditions.

Key Insights and Ideas

  • Burial Depth is a Double-Edged Sword: While deeper burial offers protection, it significantly hinders heat dissipation through the soil, leading to a predictable decrease in ampacity. This effect is more pronounced initially and then stabilizes.
  • Internal Medium Matters Dramatically: Muddy water is the champion for heat dissipation among the tested internal media, offering significantly higher ampacity than air or even seawater. This is attributed to its high thermal conductivity and ability to fill voids effectively.
  • Material Choice is Critical: Non-magnetic metallic conduits (copper, stainless steel) far outperform polymeric ones (PE, PVC) in terms of ampacity. This is due to their superior thermal conductivity, allowing heat to escape more readily.
  • Environmental Temperature is a Major Factor: Higher ambient temperatures directly reduce ampacity. This is because warmer soil has lower thermal conductivity and weakens the temperature gradient needed for efficient heat transfer away from the cable. This effect is exacerbated by potential soil desiccation in hot conditions.
  • Bottlenecks Exist: The study identified specific "monitoring points" along the cable route where ampacity is lowest, acting as critical bottlenecks for the entire system's power transmission capacity.

Key Results

  • Burial Depth: Ampacity decreased by 4.7% to 6.3% for every 0.5m increase in burial depth.
  • Internal Media: Muddy water enhanced ampacity by 22–35% compared to air-filled conditions.
  • Conduit Material: Copper and stainless steel conduits showed significantly higher ampacity than PE and PVC.
  • Environmental Temperature: A 10°C increase in surface soil temperature led to a 6.2–7.1% decrease in ampacity.
  • Model Validation: The FEM model showed an average error of 4.9% compared to the IEC-60287 standard for air-filled J-type conduits.

Limitations and Future Work

  • Simplifications: The authors acknowledge that the model involves simplifications of actual operating conditions.
  • Long-Term Operation: Future work should investigate the long-term operational characteristics of cables under real marine environmental conditions.
  • Optimization: A comprehensive balance between cable ampacity, structural stability, and economic evaluation is needed for optimized engineering solutions.
  • Hybrid Designs: The paper suggests a hybrid design strategy, using metallic conduits in critical terminal sections and polymer conduits elsewhere, to balance performance and cost.

Summary updated

Abstract

For the installation of submarine cables at sites with significant elevation differences and non-excavation bases, the J-type conduit represents an emerging installation solution. This study focused on a typical AC submarine cable installed via J-type conduit trenchless installation. A coupled electromagnetic–thermal–fluid finite element model was established to investigate the effect of the burial depth, conduit material, and environmental temperature on the ampacity of the cable. The results indicate that the ampacity of the cable decreases as the burial depth increases due to the deteriorating heat dissipation capacity of the soil. Regarding the internal medium of the conduit, the cable demonstrates superior ampacity performance in muddy water. Additionally, J-type conduits fabricated from non-magnetic metallic materials such as copper and stainless steel exhibit significantly higher cable ampacity compared to polymeric materials like PE and PVC. As the soil’s temperature rises with the increasing environment temperature, its thermal conductivity efficiency decreases, consequently impairing cable heat dissipation and ampacity.