NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Improved Inner Approximation for Aggregating Power Flexibility in Active Distribution Networks and Its Applications

Yi Guo, Yilin Wen, Zechun Hu, Jinhua He, Yi Guo 0006IEEE Trans. Smart Grid 2024

TL;DR

This paper introduces a novel inner approximation method for modeling the aggregated power flexibility of Active Distribution Networks (ADNs) at the transmission level. By leveraging the structure of the exact aggregation model (EAM), this method significantly improves computational efficiency and accuracy compared to existing approaches, making it practical for real-world applications like security-constrained unit commitment.

What Problem Does This Paper Address?

As distributed energy resources (DERs) like EVs, solar panels, and energy storage systems become more prevalent, Active Distribution Networks (ADNs) are increasingly playing a crucial role in power system operations. Effectively coordinating these ADNs with the broader transmission network requires accurately modeling the aggregated power flexibility they offer. However, the "exact aggregation model" (EAM) for this flexibility is computationally intractable due to its exponential complexity with respect to time slots. Existing approximation methods often sacrifice accuracy for tractability or are too complex for practical applications like unit commitment, which requires modeling many time steps. This paper aims to bridge this gap by developing an inner approximation method that is both accurate and computationally efficient.

Methods

The core of this paper is a novel inner approximation method for power flexibility aggregation. The approach builds upon the Exact Aggregation Model (EAM) by:

  • Prototype Selection: Instead of arbitrary geometric shapes, the method defines the approximation's geometric prototype using a subset of the coefficient vectors from the EAM. Specifically, it favors the "energy-change boundary" prototype, which is derived from EAM constraints and offers better accuracy.
  • Parameter Calculation: A key innovation is an iterative parameter calculation algorithm that leverages the structure of the EAM. This algorithm efficiently shrinks the approximated region towards the EAM's boundary, ensuring it remains fully contained (inner approximation) while maximizing its size. This process involves solving a series of optimization problems that are transformed into Mixed-Integer Linear Programming (MILP) problems.
  • Double Inner Approximation Framework: To handle the complexity of large-scale distribution networks with multiple DER aggregators, a two-level framework is proposed. The first level models the flexibility of each DER aggregator, and the second level models the aggregated flexibility at the substation level, considering both aggregator outputs and network constraints. This framework balances computational tractability and data privacy.

Datasets

Not discussed in the paper. The paper uses a modified IEEE-33 bus distribution network and an IEEE-30 bus transmission network for case studies.

Key Insights and Ideas

  • Leveraging EAM Structure is Key: The paper demonstrates that understanding and utilizing the mathematical structure of the exact aggregation model (EAM) is crucial for developing effective approximation methods. Simply using generic geometric prototypes is less effective.
  • Energy-Change Boundary Prototype: The "energy-change boundary" prototype, derived from EAM constraints, offers a significant improvement in accuracy (reduced conservatism) compared to simpler prototypes like power-energy boundaries.
  • Iterative Shrinking for Accuracy: The iterative parameter calculation method effectively shrinks the approximate feasible region towards the true EAM, ensuring feasibility while maximizing the region's size.
  • Double Approximation for Scalability: The two-level approximation framework is essential for handling the complexity of real-world distribution networks with multiple DER aggregators, enabling practical integration into transmission-level planning.
  • Trade-off Between Accuracy and Conservatism: While the double approximation framework introduces some conservatism, it is a necessary trade-off for computational tractability and data privacy, which are critical for practical implementation.

Key Results

  • Computational Efficiency: The proposed method achieves significant speedups. For T=12, computation times are 1.910s (power-energy boundary) and 3.528s (energy-change boundary), drastically lower than methods like [23] which took 35.36s and failed to converge for T=24.
  • Accuracy: The energy-change boundary prototype yields the highest relative size (0.9302), indicating the least conservatism and thus higher accuracy among tested inner approximation methods.
  • SCUC Application: When applied to a Security-Constrained Unit Commitment (SCUC) problem involving an IEEE-30 bus transmission network and 13 ADNs, the proposed method led to a cost reduction of $1,889 compared to a baseline scenario.
  • Scalability: The SCUC solution time showed minimal increase with the number of ADNs, highlighting the scalability of the proposed flexibility modeling approach due to its concise representation (only 4T-2 constraints per ADN).

Limitations and Future Work

  • Conservatism: The paper acknowledges that the double inner approximation framework, while practical, sacrifices some accuracy for tractability and data privacy.
  • Future Work: The authors suggest that using higher-precision prototypes at both levels (e.g., the energy-change boundary prototype) can mitigate the conservatism issue. Further research could explore more advanced techniques to further reduce conservatism while maintaining computational efficiency. The paper also notes that the cost of adjusting power within the feasible region of ADNs is assumed negligible, which could be incorporated in future work.

Summary updated

BibTeX
@article{guo2024improved,
  author = {Yi Guo and Yilin Wen and Zechun Hu and Jinhua He and Yi Guo},
  title = {{Improved Inner Approximation for Aggregating Power Flexibility in Active Distribution Networks and Its Applications}},
  journal = {IEEE Trans. Smart Grid},
  year = {2024},
  doi = {10.1109/tsg.2023.3340157},
}
Figure