Impact of Window-Opening Behaviors on Energy Consumption in Primary School Classrooms

Zhen Peng, Pei Li, Tong He, Mingli Liu, Liu Hai-ping, Mingzhe Jiang, Rui ZhangEnergies 2025

TL;DR

This study quantifies the significant energy loss (12.83 kWh/day in winter) caused by window-opening behaviors in primary school classrooms. By combining field measurements, CFD simulations, and PMV analysis, it reveals how temperature, humidity, and other factors influence these behaviors, offering data-driven strategies to optimize window use for energy savings and thermal comfort.

What Problem Does This Paper Address?

Global climate change necessitates reducing energy consumption, and educational buildings are significant energy consumers. While much research focuses on commercial or residential buildings, primary schools present unique challenges due to high occupant density, continuous movement, and variable usage patterns. A critical, yet often overlooked, factor influencing energy consumption in these spaces is occupant behavior, specifically how and when windows are opened or closed. This behavior can lead to substantial energy loss, particularly during heating seasons, and existing research often lacks detailed, real-world data from educational settings or comprehensive analysis of the dynamic interplay between behavior and environmental factors. This paper aims to fill that gap by investigating window-opening behaviors in primary school classrooms and their direct impact on energy consumption.

Methods

The researchers employed a multi-faceted approach:

  • Field Measurements: Wireless smart sensors were installed in a primary school classroom to collect real-time data on door and window opening/closing events. Simultaneously, indoor and outdoor environmental parameters (temperature, humidity, PM2.5, PM10, CO2) were monitored.
  • CFD Simulations: Computational Fluid Dynamics (CFD) was used to simulate the outdoor wind environment and its pressure on the classroom windows under various wind conditions (winter west/south, summer south/southeast). This was followed by internal CFD simulations to analyze airflow patterns within the classroom based on different window opening configurations.
  • Energy Loss Quantification: A heat exchange model was used to calculate energy loss due to window openings, integrating data from environmental monitoring, CFD simulations, and window opening records.
  • PMV Model Analysis: The Predicted Mean Vote (PMV) model was applied to assess thermal comfort levels associated with different window opening scenarios during winter, aiming to identify combinations that achieve thermal neutrality.
  • Binary Logistic Regression: This statistical model was used to analyze the relationship between environmental factors (temperature, humidity, PM) and the probability of windows being open or closed.

Datasets

The study utilized data collected from a single case study primary school classroom in Weifang City, Shandong Province, China. This included:

  • Window and Door Opening/Closing Data: Collected via wireless smart sensors over a 20-day period in summer (June-July 2023) and a 61-day period in winter (November-December 2023).
  • Environmental Data: Indoor and outdoor temperature, humidity, PM2.5, PM10, and CO2 concentrations, recorded every 5 minutes.
  • External Wind Data: Meteorological data for wind speed and direction distribution in the region.

No new benchmark datasets were introduced; the focus was on collecting novel, real-world data from the specific context of a primary school classroom.

Key Insights and Ideas

  • Window Behavior is a Major Energy Drain: The study highlights that simple actions like opening windows during winter heating can lead to substantial energy losses (12.83 kWh per day for a single classroom), underscoring the need for occupant awareness and optimized strategies.
  • Seasonal Differences in Behavior: Window opening and closing patterns differ significantly between summer and winter, driven by distinct ventilation needs (cooling vs. heating). Summer sees more frequent and longer openings, while winter openings are less frequent and shorter, though still impactful.
  • Temperature's Dual Role: In summer, higher temperatures lead to decreased window opening (to block heat), while in winter, higher temperatures initially increase opening probability (for ventilation) but then decrease it once the indoor heating threshold is exceeded, suggesting a complex interplay with thermal comfort.
  • Humidity as a Driver: In summer, rising indoor humidity strongly encourages window opening to reduce moisture, a key factor for comfort.
  • PM Levels Have Less Impact Than Expected: While PM concentrations were monitored, their influence on window-opening behavior in summer appeared less significant than temperature and humidity, suggesting thermal comfort often takes precedence.
  • Optimizing Winter Openings: The PMV analysis identified specific window opening combinations (e.g., C2 and C4) that are most likely to achieve thermal neutrality in winter, providing actionable insights for energy-saving strategies without sacrificing comfort.

Key Results

  • Significant Winter Energy Loss: Daily energy loss due to external window openings during the winter heating period was quantified at 12.83 kWh per classroom. Over the entire heating period, this amounted to 436.06 kWh for one classroom.
  • High Prediction Accuracy: Binary logistic regression models showed high prediction accuracy (often >0.9) for the relationship between environmental factors and window opening probabilities, particularly for windows C5 and C6.
  • Summer vs. Winter Behavior: Window opening duration and frequency were generally higher in summer than in winter.
  • PMV Neutrality: For winter conditions, scenarios W4, W3, and W2 showed probabilities of thermal neutrality of 79.84%, 20.1%, and 0.07% respectively, with average PMV values of 0.10, 0.29, and 0.08.

Limitations and Future Work

  • Single Case Study: The study was conducted in one classroom, limiting the generalizability of findings across diverse school types and climates. Future work should include more classrooms and schools.
  • Limited Measurement Period: The monitoring periods were constrained by school schedules. Longer durations and inclusion of transitional seasons would provide more robust data.
  • Simulation Simplifications: Only dominant wind directions were considered in CFD simulations. More comprehensive analysis including less frequent conditions is needed.
  • Energy Loss Simplification: Energy loss calculations primarily focused on temperature differences, excluding other heat transfer mechanisms.
  • Child-Specific Comfort: The PMV model's assumptions on metabolic rates and clothing may not fully capture children's unique thermal preferences and behaviors. Future research should incorporate child-specific data and adaptive models.
  • Contradictory Relationships: Some factors showed contradictory relationships with window openings, requiring further investigation.
  • Broader Climate Zones: Future studies should expand to various climate zones in China to comprehensively analyze window-opening behaviors and develop region-specific energy-saving strategies.

Summary updated

Abstract

In the context of global climate warming, the issue of building energy consumption has become increasingly prominent, with a particular focus on energy management in educational buildings. This study investigates the impact of window usage behaviors in primary school classrooms on building energy consumption, aiming to reveal the dynamic relationship between window-opening behaviors and energy consumption, as well as to propose optimization strategies. A case study was conducted at a primary school, where data on door and window behaviors were collected using wireless smart sensors. Combined with indoor and outdoor environmental monitoring and CFD simulations, this study quantified the impact of window-opening behaviors on building energy consumption. The findings revealed that, in summer, window-opening behaviors exhibited a negative correlation with both indoor and outdoor temperature and humidity. Under high-temperature conditions, individuals tend to close windows to reduce heat entry. In contrast, winter window-opening behaviors showed a positive correlation with indoor and outdoor temperatures, although the probability of opening windows decreased once the temperature exceeded a certain threshold. This study also found that during the winter heating period, energy losses caused by opening external windows were substantial, with daily energy losses amounting to 12.83 kWh. Based on the PMV model, this study proposed an optimization strategy for opening specific windows during winter to maintain thermal comfort. This research provides a scientific basis for the energy-saving design of primary school buildings, helping to reduce energy waste while ensuring indoor comfort and promoting the development of low-carbon campuses.
BibTeX
@inproceedings{peng2025impact,
  author = {Zhen Peng and Pei Li and Tong He and Mingli Liu and Liu Hai-ping and Mingzhe Jiang and Rui Zhang},
  title = {{Impact of Window-Opening Behaviors on Energy Consumption in Primary School Classrooms}},
  booktitle = {Energies},
  year = {2025},
  doi = {10.3390/en18082050},
}
Figure