Frequency-Reactive Power Optimization Strategy of Grid-forming Offshore Wind Farm Using DRU-HVDC Transmission

Zhekai Li, Kun Han, Xu Cai, Renxin Yang, Haotian Yu, Kepeng Xia, Lulu LiuarXiv 2024 · DOI · arXiv

Introduction

As offshore wind farms (OWFs) move further from the coast, the cost and complexity of power transmission increase significantly. While Modular Multilevel Converter (MMC) HVDC systems are currently the standard, their massive size and weight lead to high installation and maintenance costs on offshore platforms. The Diode Rectifier Unit (DRU) HVDC system offers a more compact, lightweight, and cost-effective alternative. However, DRUs are passive devices that cannot establish an AC grid. To overcome this, wind turbines must employ Grid-Forming (GFM) control to autonomously create and maintain the offshore AC network.

System Architecture and Grid-Forming Control

In a DRU-HVDC configuration, the wind turbines are responsible for frequency and voltage regulation. This paper focuses on GFM wind turbines that utilize a specific control strategy to manage the "inverted" power flow characteristics of the DRU. Unlike traditional grids where active power is primarily linked to frequency, in a DRU-based system, active power flow is dominated by voltage amplitude, while reactive power flow is closely coupled with frequency.

The control architecture of a GFM wind turbine, highlighting the $\omega-Q$ self-balance control block used for frequency-reactive power coordination.

The control system shown in Figure 2 integrates a Phase-Locked Loop (PLL) and an $\omega-Q$ self-balance control loop. This allows the turbine to adjust its internal frequency based on reactive power demands, effectively using frequency as a control variable to optimize the network's operation.

Optimization Methodology

The researchers developed an Optimal Power Flow (OPF) model tailored for the unique characteristics of the DRU-HVDC system. The model accounts for the coupling between the internal network frequency and the reactive power output of the GFM turbines.

A key challenge in this optimization is the non-convex nature of the power flow equations, particularly those describing the diode characteristics. To solve this efficiently, the authors employed Taylor expansion to linearize the diode model and applied Second-Order Cone Programming (SOCP) relaxation. This transformation converts the complex, non-linear problem into a convex one that can be solved reliably using standard toolkits like YALMIP and CPLEX.

Relationship between total reactive power demand and internal network frequency across various active power output levels ($P_{farm}$).

As illustrated in Figure 4, the reactive power demand of the wind farm integration net is approximately linear with respect to frequency within the operating range. By slightly shifting the frequency (e.g., between 0.9995 and 1.0001 p.u.), the system can redistribute reactive power to minimize overall network losses.

Key Results and Discussion

The proposed optimization strategy was tested using parameters from a real-world offshore wind project over a simulated 24-hour cycle. The results demonstrate a significant improvement in efficiency:

  • Loss Reduction: The strategy achieved a reduction in network power losses exceeding 25.3% compared to conventional control methods.
  • Operational Efficiency: The optimization is most impactful during periods of moderate to high wind turbine output (50% to 70% load), where reactive power management is most critical.
  • System Stability: The GFM turbines successfully maintained autonomous frequency construction and synchronization throughout the optimized period, even with the dynamic frequency adjustments.

Conclusion

This research provides a robust framework for optimizing the operation of DRU-HVDC offshore wind farms. By leveraging the unique frequency-reactive power coupling of GFM turbines, the proposed strategy significantly reduces energy losses without requiring expensive additional hardware. Future work will focus on refining these models for heterogeneous wind farms and validating the strategy through experimental hardware-in-the-loop testing.

Summary updated

BibTeX