Flexibility of Commercial Building HVAC Fan as Ancillary Service for Smart Grid

Mehdi Maasoumy, Jorge Ortiz, David E. Culler, Alberto L. Sangiovanni-VincentelliarXiv 2013

TL;DR

This paper demonstrates that commercial building HVAC fans can provide valuable ancillary services to the smart grid by modulating their power consumption without negatively impacting indoor comfort. Experiments and simulations suggest that this untapped flexibility could contribute gigawatts of regulation reserve, significantly enhancing grid stability and enabling greater renewable energy integration.

What Problem Does This Paper Address?

The increasing penetration of renewable energy sources (RES) like solar and wind introduces significant volatility and intermittency into the power grid. This makes it challenging to maintain the instantaneous balance between electricity generation and demand, which is crucial for grid stability. Ancillary services, such as frequency regulation, are essential for managing these fluctuations. Traditionally, these services have been provided by power plants, but this paper explores a novel and underutilized resource: the HVAC systems in commercial buildings. The challenge is to determine if and how these systems can reliably provide these services without compromising occupant comfort or building operations.

Methods

The authors employed a two-pronged approach:

  1. At-Scale Experiments: They conducted experiments on the HVAC system of a real commercial building (Sutardja Dai Hall at UC Berkeley). Specifically, they modulated the Supply Duct Static Pressure (SDSP) set-point, which directly influences the speed and power consumption of the main supply fans. This allowed them to measure the fan's response and its impact on indoor temperatures.
  2. Mathematical Modeling and Simulation: They developed a single-input, single-output (SISO) ARX model to represent the relationship between SDSP and fan power consumption, using data from their experiments. This model was then integrated into a simplified power system simulation to evaluate the effectiveness of building HVAC systems in providing frequency regulation services. They also incorporated models for standard power system components like governors, turbines, and generators.

Datasets

The primary dataset used in this paper was collected from empirical data captured through the sMAP (sensor Measurement and Actuation Profile) system at UC Berkeley's Sutardja Dai Hall. This included measurements of:

  • Supply Duct Static Pressure (SDSP) set-point (control input)
  • HVAC fan power draw (output)
  • Internal temperatures of 10 randomly sampled rooms

This data was used for both identifying the ARX model of the fan and for validating the impact of fan modulation on indoor climate.

Key Insights and Ideas

  • Untapped Flexibility in HVAC Fans: Commercial building HVAC fans, which represent a significant portion of a building's energy consumption, can be modulated to provide ancillary services without noticeable impact on occupant comfort. This is a substantial, readily available resource.
  • Fast Response Capability: HVAC fans, particularly when controlled via SDSP, can respond very quickly (on the order of seconds) to grid signals, making them suitable for fast frequency regulation.
  • Minimal Comfort Impact: Experiments showed that modulating fan speed within safe pressure boundaries had negligible effects on internal room temperatures, staying within typical comfort ranges. This is attributed to the "thermal slack" within buildings.
  • Cost-Effectiveness: Providing these services through HVAC fans is essentially "free" as it doesn't require additional energy consumption or specialized equipment beyond existing variable frequency drives and building management systems.
  • Scalability: The potential for ancillary services from commercial buildings is enormous. Even a small fraction of buildings equipped with variable frequency drives could contribute gigawatts of regulation reserve.

Key Results

  • Ancillary Service Potential: Each HVAC fan can provide approximately 18% of its nominal power draw as flexibility (12 kW out of 67 kW for the SDH building's main fans).
  • US-Wide Estimate: Based on 2003 data, it's estimated that at least 4 GW of fast ancillary service is readily available from commercial buildings in the US. This is projected to increase to 5.6 GW by 2035.
  • Comfort Preservation: Experiments demonstrated that fan speed modulation had no observable impact on internal room temperatures, confirming the hypothesis that thermal slack can absorb these changes.
  • Simulation Effectiveness: Simulations showed that incorporating building-based ancillary services significantly improved grid frequency regulation compared to scenarios without it, especially with higher levels of available ancillary power.

Limitations and Future Work

  • Model Simplification: The ARX model used is a simplified representation of the fan dynamics. While effective for this study, more complex models might be needed for highly dynamic or diverse HVAC systems.
  • Generalizability: While experiments were conducted on one building, the authors acknowledge the need for further validation across a wider range of commercial building types and HVAC configurations.
  • Control Strategy Sophistication: The paper uses a simple proportional control for ancillary service flow. Future work will focus on developing more sophisticated model predictive control (MPC) frameworks.
  • Integration Challenges: Future research will explore integrating building HVAC flexibility with other grid services, considering factors like real-time frequency, generation ramping rates, load forecasting, and energy pricing.
  • Contractual Frameworks: The authors plan to develop contractual frameworks for utilities and building operators to formalize the provision and reward of ancillary services.

Summary updated

Abstract

In this paper, we model energy use in commercial buildings using empirical data captured through sMAP, a campus building data portal at UC Berkeley. We conduct at-scale experiments in a newly constructed building on campus. By modulating the supply duct static pressure (SDSP) for the main supply air duct, we induce a response on the main supply fan and determine how much ancillary power flexibility can be provided by a typical commercial building. We show that the consequent intermittent fluctuations in the air mass flow into the building does not influence the building climate in a human-noticeable way. We estimate that at least 4 GW of regulation reserve is readily available only through commercial buildings in the US. Based on predictions this value will reach to 5.6 GW in 2035. We also show how thermal slack can be leveraged to provide an ancillary service to deal with transient frequency fluctuations in the grid. We consider a simplified model of the grid power system with time varying demand and generation and present a simple control scheme to direct the ancillary service power flow from buildings to improve on the classical automatic generation control (AGC)-based approach. Simulation results are provided to show the effectiveness of the proposed methodology for enhancing grid frequency regulation.
BibTeX
@misc{maasoumy2013flexibility,
  author = {Mehdi Maasoumy and Jorge Ortiz and David E. Culler and Alberto L. Sangiovanni-Vincentelli},
  title = {{Flexibility of Commercial Building HVAC Fan as Ancillary Service for Smart Grid}},
  year = {2013},
  eprint = {1311.6094},
  archivePrefix = {arXiv},
  url = {https://arxiv.org/abs/1311.6094},
}
Figure