Feature Extraction and Analysis of PRPD Spectrum from Pulse-Current Measurements

Bodong Chen, Kang Liu, GuangQi Lu, X. Rosalind Wang, Di Zhao2025

Abstract

High-voltage switchgear is foundational to distribution-network safety, and partial-discharge (PD) monitoring is regarded as essential for preventing insulation failures. A pulse-current PD test platform was developed for switchgear, and a reproducible PRPD spectrum dataset spanning four canonical defect types—surface, tip, gas-gap, and floating discharges—was assembled. From the PRPD spectra, six global statistics were derived—the positive/negative half-cycle phase-centroid ratio, phase-standard-deviation ratio, phase-entropy ratio, skewness, kurtosis, and cross-correlation coefficient—and class separability was evaluated using box-plot analysis. To mitigate redundancy and multicollinearity, feature pruning/selection was performed with Spearman rank correlation and the variance inflation factor (VIF) within cross-validation. No single feature was found to yield stable classification; instead, a compact four-feature subset—centroid ratio, entropy ratio, kurtosis, and cross-correlation—was identified that achieves VIF < 4, exhibits only weak-to-moderate pairwise correlations, and provides strong complementarity, yielding a stable and interpretable basis for downstream classification of insulation defects in high-voltage switchgear.