Fault Ride-Through Strategy of MMC in Series with DR for Offshore Wind Farms
Abstract
Compared with the conventional MMC, a DR in series with MMC DC transmission system is highly promising because it has a smaller MMC voltage level and capacity, leading to drop in construction cost. However, there is a lack of literature on its AC fault ride-through strategy. In this paper, a fault ride-through strategy for DR in series with MMC systems based on the active energy control of MMC is proposed, considering the characteristics of DR. Firstly, the topology of DR in series with MMC system and the active energy control strategy are introduced. Subsequently, the fault ride-through strategy applicable to this system is proposed based on the feature that the capacitive energy of MMC sub modules can reach 2.25 pu in a short time. And the preset curves account for the smaller capacity of the offshore MMC and the coupling between the DR AC voltage, DC current and DC voltage. Finally, simulation results from MATLAB/SIMULINK with different types of AC faults demonstrate the reliability of the proposed strategy.
BibTeX
@misc{wang2024fault,
author = {Yanfeng Wang and Ziquan Wang and Chenghao Xu and Mengze Yu and Songtao Wang and Jinyu Wang and Junyi Sheng},
title = {{Fault Ride-Through Strategy of MMC in Series with DR for Offshore Wind Farms}},
year = {2024},
doi = {10.1109/repe62578.2024.10809866},
}Ask Althea to put this paper to the test.