Abstract
Identifying faults in distribution networks is critical for maintaining grid stability. This paper proposes a novel method using a mixture of von Mises–Fisher (mov-MF) distribution models to identify fault probabilities. By leveraging synchronous phasor measuring units (PMUs) to collect post-fault steady-state voltage phase angles, the method constructs three-dimensional feature vectors. These vectors are mapped onto a unit sphere and modeled using the mov-MF distribution, optimized via spherical K-means and expectation–maximization (EM) algorithms. Validation on the IEEE 33-node system demonstrates high accuracy across various fault types, including single-phase ground and multi-phase short circuits, even under high transition resistance.
Introduction
Distribution networks serve as the final link in the power delivery chain, making them highly susceptible to diverse fault conditions. Traditional identification methods often struggle with feature complexity, relying on 1D or 2D signals that require extensive preprocessing. Furthermore, many approaches ignore the rich information embedded in phase angles, focusing solely on magnitudes. This research addresses these gaps by treating fault data as directional statistics on a 3D sphere.
Methodology: Directional Feature Mapping
The core innovation involves extracting positive, negative, and zero sequence voltage phase angles (φ1, φ2, φ3) from PMU data. These are L2-normalized to reside on the surface of a 3D unit sphere. Unlike linear Gaussian models, the von Mises–Fisher (vMF) distribution is specifically designed for such directional data.
The mov-MF model acts as a spherical equivalent to a Gaussian Mixture Model. The optimization pipeline uses Spherical K-means and Minimum Message Length (MML) for initialization, followed by the Expectation-Maximization (EM) algorithm to refine the mean direction and concentration parameters.
Results and Robustness
The method was tested using a simulated IEEE 33-node 10-kV distribution system. The model achieved near-perfect accuracy (96.39% to 100%) for standard faults. A key strength is its robustness to high transition resistance; even at 1000Ω, the system maintained a 94.44% accuracy rate for single-phase grounding.
Furthermore, the integration of Distributed Generation (DG), such as solar PV, showed negligible impact on identification performance. The computational efficiency is also notable, with fault identification occurring in under one second, making it suitable for real-time applications.
Conclusion
By utilizing directional statistics and the mov-MF distribution, this method provides a mathematically transparent and computationally efficient alternative to "black-box" deep learning models. Future work will focus on validating the model against real-world sensor noise and more complex, evolving fault scenarios.