Experimental Study on Bending Resistance of New Type Joint of Prestressed Concrete Pipe Pile

Bo Wang, Lei Qi, Yongdong YangSymmetry 2022 · DOI

TL;DR

This paper introduces and tests a novel clamping joint for prestressed high-strength concrete (PHC) pipe piles, designed to be flush with the pile surface, addressing issues with traditional protruding joints. Experimental and finite element analyses demonstrate that this new joint exhibits good bending resistance, with cracks primarily occurring in the pile body rather than the joint itself, suggesting improved structural integrity.

What Problem Does This Paper Address?

Traditional PHC pipe pile joints often feature protruding elements (like bamboo-like hoops) that can cause significant problems during pile installation. These protrusions can disturb the surrounding soil, negatively impacting frictional resistance and potentially leading to installation difficulties. The paper aims to solve this by proposing and evaluating a new type of clamping joint that is flush with the pile's outer surface, thereby mitigating these installation-related issues and improving the overall performance of the pile joint under bending loads.

Methods

The study employed a multi-faceted approach:

  • Novel Joint Design: A new clamping joint design was developed, featuring semicircular clamps and end plates that create a flush connection. A method for determining the optimal dimensions of this new joint was also presented.
  • Experimental Testing: Four types of PHC pipe pile specimens, each incorporating the new joint, were subjected to pure bending tests. These tests aimed to observe the deformation process, bending capacity, and damage characteristics.
  • Finite Element Analysis (FEA): ABAQUS software was used to create a numerical model of the pile and joint system. This FEA was used to simulate the bending behavior and validate the experimental findings. Material properties for concrete and steel were defined based on experimental values and standard engineering practices.
  • Strain and Deflection Measurement: During the experiments, strain gauges were strategically placed on the joint and pile body, and displacement gauges were used to measure deflections at key points to capture the structural response.

Datasets

Not discussed in the paper. The study relies on experimental data generated from the tested specimens and simulated data from the FEA.

Key Insights and Ideas

  • Flush Joint Advantage: The proposed clamping joint, being flush with the pile surface, effectively eliminates the soil disturbance issues associated with traditional protruding joints, which is a significant practical improvement for pile installation.
  • Joint Integrity Under Bending: The experimental results indicate that the new joint is robust. Under bending loads, cracks primarily initiate and propagate within the pile body, particularly in the pure bending section, rather than at the joint itself. This suggests the joint is not the weak link in the system.
  • Symmetrical Damage: Observed crack patterns were largely symmetrical on both sides of the joint, indicating a predictable and uniform stress distribution around the connection.
  • Deflection Behavior: Under the same bending moment, the deflection at the mid-span of the pile was consistently greater than the deflection at the loading point, a common behavior in beam-like structures under load.

Key Results

  • Bending Capacity: The new joint design demonstrated good bending resistance. The ultimate bending moments at which cracks appeared varied across the four specimen types (A-D), ranging from 96 kN·m to 210 kN·m.
  • Crack Characteristics: Cracks were predominantly vertical and located in the pure bending section. For specimen A, cracks were 0.46 mm wide and 270 mm long at failure. For specimen C, cracks reached 0.73 mm in width and 290 mm in length.
  • Strain Distribution: Strain analysis showed that the joint primarily experiences tension under pure bending. Strain gauge readings indicated increasing tensile and compressive strains with increasing load.
  • FEA Validation: The finite element analysis results closely matched the experimental data, particularly in terms of the bending moment-displacement curves. While the FEA curves generally lay slightly below the test curves (likely due to the FEA not fully accounting for accumulated damage in concrete during the test), the ultimate bearing capacity predictions were consistent.

Limitations and Future Work

  • Damage Modeling: The authors acknowledge that the finite element simulation did not fully account for accumulated damage in the concrete during the test, which might explain the slight discrepancy between FEA and experimental results.
  • Limited Scope of Testing: While the study focused on bending resistance, further research could explore the joint's performance under other loading conditions, such as axial loads, shear, or combined loads, which are more representative of real-world scenarios.
  • Material Variations: The study tested specific concrete strengths and reinforcement types. Investigating the joint's performance with a wider range of materials could provide broader applicability.
  • Long-Term Performance: The paper does not discuss the long-term durability or performance of the joint under cyclic loading or environmental exposure.

Future work could involve extending the FEA to incorporate more sophisticated damage models for concrete and conducting tests under more complex loading scenarios to fully characterize the joint's behavior in various engineering applications.

Summary updated

Abstract

In the field of PHC pile joints, it is important that prestressed high-strength concrete pipe piles are referred to as PHC pipe piles. In conventional hoops, bamboo-like joints protrude from the pile joint position at the surface of the pile. Driving the pile in, disturbing the soil around the pile, and affecting the frictional resistance are serious issues. To address such issues, herein, a new type of clamping joint is proposed. A new method is presented to determine the size of the new joint that is flushed with the surface of the pile at the joint position. Bending resistance tests are conducted on four types of new joints for common pipe piles to study the deformation development process, bending bearing capacity, and damage characteristics of the new joints. Cracks are mainly distributed in the pure bending section and are approximately symmetrically distributed along both sides of the joint; there is no obvious cracking and damage in the joint until the pile cracks. Under the same bending moment, the deflection in the span of all specimens is greater than the deflection at the loading point.