NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Experimental Research on Partial Discharge of High Voltage Direct Current

Jian Zhang, Minhu Xu, Yun Guo, Kexin Zhang, Heqian Liu, Xiangyu ZhaoJournal of Physics Conference Series 2021

Abstract

Abstract Under the action of long-term high-voltage DC voltage, the insulation of electrical equipment is inevitably aging, and it is necessary to monitor its insulation status. Since insulation defects of different nature damage electrical equipment to different degrees, the identification of defects is very important. To this end, a DC partial discharge detection system based on AC partial discharge detection equipment was built, focusing on key issues such as the choice of test power supply, the choice of test frequency, and the choice of pressurization methods. The successful completion of the on-site partial discharge test of UHV converter transformers has provided valuable practical experience for the future on-site partial discharge tests of UHV converter transformers, and provided important tests for the establishment of on-site partial discharge test standards for UHV converter transformers. in accordance with.
BibTeX
@article{zhang2021experimental,
  author = {Jian Zhang and Minhu Xu and Yun Guo and Kexin Zhang and Heqian Liu and Xiangyu Zhao},
  title = {{Experimental Research on Partial Discharge of High Voltage Direct Current}},
  journal = {Journal of Physics Conference Series},
  year = {2021},
  doi = {10.1088/1742-6596/1865/2/022026},
}

Loading related content...