Abstract
This paper investigates the issues of the distributed energy management problem (EMP) of Microgrids in the presence of communication delays. To address this issue, a consensus-based distributed algorithm is proposed to integrate the economic dispatch and demand response, which can optimally assign the energy among generation units and load units with the objective of maximizing the total social welfare of the power system. Different from existing energy management algorithms, a nonuniform time-varying delays model is considered and embedded into the design of our algorithm, such that each unit can achieve collaborative optimization without the requirement of fixed delays information, which has both theoretical merits and practical engineering value for the efficient and stable operation of Microgrids. Moreover, it is proved that the proposed algorithm can converge to the optimal solution under some sufficient conditions. Finally, the correctness and effectiveness of the proposed method are validated by several simulation results.
Introduction
The modernization of power systems has led to the rise of microgrids, which integrate diverse renewable energy sources and flexible loads. Managing these systems efficiently requires solving the Energy Management Problem (EMP), traditionally handled by centralized controllers. However, centralized approaches suffer from single-point-of-failure risks, poor scalability, and privacy concerns. Distributed management, where units reach a consensus through local communication, offers a more robust alternative.
A critical challenge in distributed control is the presence of communication delays. Real-world networks experience non-uniform, time-varying delays due to congestion and physical distance. If not properly addressed, these delays can lead to system oscillations or instability. This paper proposes a consensus-based distributed algorithm specifically designed to maintain stability and optimality under such conditions.
Methodology and System Architecture
The proposed algorithm integrates Economic Dispatch (minimizing generation costs) and Demand Response (maximizing user utility) into a unified framework. It aims to maximize total social welfare while accounting for system power losses.
Algorithm Design
The core of the approach is a consensus-based model using auxiliary variables ($\varsigma_i$) and consensus variables ($\lambda_i$). Each unit calculates its optimal power output or consumption locally, relying only on information exchanged with immediate neighbors. Unlike standard models, this algorithm embeds a non-uniform time-varying delay model ($\tau_{ij}(t)$) directly into its structure.
The stability of the system is mathematically guaranteed using Lyapunov-Krasovskii functionals and Linear Matrix Inequalities (LMIs). These tools prove that the system converges to a global optimum provided the delays remain within a calculated upper bound and the rate of change of the delay is less than one.
Constraint Handling
To respect physical limits, such as maximum generator capacity, a three-step iterative process is employed. This process uses average consensus to re-adjust the system when specific units hit their operational boundaries, ensuring the global power balance is maintained.
Simulation and Performance Evaluation
The algorithm was validated using a simulated microgrid testbed. The configuration included three traditional generators (G1, G2, G3), one renewable generator (G4) providing a constant 58MW, and two flexible loads (D5, D6).
Accuracy and Convergence
In comparative studies, the distributed algorithm achieved an optimal incremental cost of 15.8201 $/MWh, which is nearly identical to the theoretical centralized solution of 15.8202 $/MWh. This demonstrates that the distributed approach does not sacrifice accuracy for robustness.
Robustness to Delays
The simulations confirmed that the system remains stable under time-varying delays (e.g., 1.8s). The research identified a "Maximum Allowable Communication Delay" (MAD) for the test case, which was approximately 2.545 seconds. Exceeding this threshold led to instability, highlighting the importance of the delay-robust design.
Plug-and-Play Capability
The system's resilience was tested by simulating unit failures. When generator G2 was removed, the remaining units automatically re-optimized their outputs to reach a new optimal state (22.0150 $/MWh) within seconds, demonstrating true "plug-and-play" functionality.
Conclusion
This paper presents a robust distributed algorithm for microgrid energy management that effectively handles non-uniform time-varying communication delays. By integrating economic dispatch and demand response, the method maximizes social welfare while ensuring system stability. Future work will focus on incorporating energy storage systems, time-of-use pricing, and more sophisticated stochastic models for intermittent renewable energy sources.
Summary updated