DC / DC converters as DC circuit-breakers in HVDC networks operation

Miguel Jiménez Carrizosa, Jorge Cortés, Abdelkrim Benchaib, P. Alou, Gilney Damm, J.a. Cobos, Françoise Lamnabhi‐Lagarrigue2014

TL;DR

This paper proposes a novel concept of using bidirectional DC/DC converters, specifically the Dual Active Bridge (DAB) topology, as DC circuit breakers in Multi-Terminal High Voltage DC (MT-HVDC) grids. By leveraging the inherent zero-crossing characteristics of the converter's internal current, this approach offers a safer and more efficient method for fault interruption compared to traditional DC circuit breakers.

What Problem Does This Paper Address?

The increasing integration of renewable energy sources, which are often intermittent and variable, is driving the need for more robust and flexible power grids. HVDC transmission is becoming more attractive for long-distance power transfer and for connecting these distributed renewable sources. Multi-Terminal HVDC (MT-HVDC) grids, which allow for more complex interconnections, are seen as the future. However, a critical challenge for MT-HVDC grids is the lack of reliable and efficient DC circuit breakers. Unlike AC systems, DC systems lack natural zero-crossings of current, making fault interruption difficult and potentially leading to damaging electric arcs. Existing solutions are often complex or have limitations. This paper addresses the need for a safe, selective, and efficient DC circuit breaker for MT-HVDC networks by proposing the repurposing of bidirectional DC/DC converters.

Methods

The core of the proposed solution lies in the modeling and control of a bidirectional DC/DC converter based on the Dual Active Bridge (DAB) topology. The authors employ a robust nonlinear control strategy based on Lyapunov theory to ensure stable operation and desired power flow regulation. This control allows the converter to track a reference current, which is crucial for both normal operation and fault interruption.

The key innovation is the utilization of the DAB converter's inherent ability to achieve zero-current crossings. This is achieved by controlling the phase shift between the voltages applied to the converter's internal transformer. When a fault is detected, the control strategy is adapted to drive the converter's internal current to zero, allowing the semiconductor switches to open safely and interrupt the fault current. This approach aims to minimize the electric arc and improve the selectivity of the fault isolation.

The paper also details simulations to evaluate the converter's robustness to disturbances and its performance as a power flow controller. For the DC circuit breaker functionality, simulations of short-circuit scenarios are presented, both with and without the proposed DC/DC converter-based circuit breaker.

Datasets

Not discussed in the paper. The paper relies on simulations using SIMULINK-MATLAB and SIMetrix/SIMPLIS environments, with parameters derived from tables and existing literature.

Key Insights and Ideas

  • DC/DC Converters as Circuit Breakers: The most significant insight is the novel concept of using bidirectional DC/DC converters, specifically DABs, as DC circuit breakers. This leverages existing components for a new critical function.
  • Zero-Crossing for Safe Interruption: The paper highlights how the internal AC stage of the DAB converter can be controlled to achieve zero-current crossings, enabling safe and efficient interruption of DC fault currents, thereby reducing electric arc severity.
  • Robust Nonlinear Control: The use of Lyapunov-based nonlinear control provides a robust framework for regulating the converter's operation, ensuring stability even under disturbances, which is essential for grid applications.
  • Selectivity and Integration: The proposed method offers the potential for selective fault isolation within MT-HVDC networks, contributing to overall grid stability and reliability.
  • Plug-and-Play Capability: The concept aligns with the vision of future MT-HVDC networks that can be easily integrated and expanded, suggesting a "plug-and-play" philosophy.

Key Results

  • Robustness to Disturbances: Simulations demonstrated that the proposed nonlinear control is robust to voltage variations (up to 20%) in the system, maintaining the current close to its reference.
  • Power Flow Control: The paper shows that the DC/DC converter can effectively regulate power flow between terminals by adjusting the current reference.
  • DC Circuit Breaker Performance: Simulations of short-circuit events showed that when the DC/DC converter is used as a circuit breaker, the fault current is interrupted safely. The time to detect and interrupt the fault (τ₁ + τ₂) was shown to be in the order of milliseconds, which is crucial for grid protection.
  • Comparison with No Breaker: Simulations clearly illustrate the detrimental effects of an unchecked short circuit spreading through the system when no DC circuit breaker is present, compared to the controlled interruption achieved with the proposed method.

Limitations and Future Work

  • Switching Frequency and Response Time: The paper acknowledges that the response time of the DC circuit breaker is influenced by the detection time of the fault and the switching frequency of the semiconductors. Increasing the switching frequency could lead to faster and more effective breaker operation.
  • Transformer Behavior During Short Circuit: The authors suggest that future work should investigate the transformer's behavior during short-circuit events.
  • Cost-Benefit Analysis: While the paper mentions that using multiple DC/DC converters increases installation cost, a detailed cost-benefit analysis is not provided.
  • Real-World Implementation: The study is based on simulations. Further research and validation through experimental setups would be necessary to confirm the practical feasibility and performance of the proposed concept.

Summary updated

BibTeX
@misc{carrizosa2014dc,
  author = {Miguel Jiménez Carrizosa and Jorge Cortés and Abdelkrim Benchaib and P. Alou and Gilney Damm and J.A. Cobos and Françoise Lamnabhi‐Lagarrigue},
  title = {{DC / DC converters as DC circuit-breakers in HVDC networks operation}},
  year = {2014},
  doi = {10.1109/epe.2014.6910762},
}
Figure