Abstract
A reasonable islanding strategy is the final resort for preventing cascading failures and large-area blackouts in interconnected power systems. This paper proposes a new Wide-Area Measurement System (WAMS)-based controlled islanding scheme. The approach defines four similarity indexes associated with generator trajectories and utilizes entropy theory to determine their weights objectively. A coherency identification algorithm based on hierarchical clustering is then presented to determine coherent groups of generators, allowing for dynamic, data-driven grid splitting that minimizes power flow disruption.
Introduction
When a major disturbance occurs in a power grid, it can trigger a cascading failure, leading to massive blackouts. Controlled islanding is a strategic "final resort" defense: operators intentionally trip specific transmission lines to create independent, stable "islands." The primary challenge lies in determining the optimal cutset—where to split the grid—to maintain stability while minimizing the imbalance between generation and load.
Traditional methods often rely on "slow coherency," which groups generators based on fixed mechanical properties and network topology. However, real-world disturbances are dynamic; generators that usually stay in sync may behave differently depending on the fault's location. Existing static methods often fail to account for real-time trajectories (angles and speeds), leading to suboptimal splits that can cause further instability.
Methodology
The proposed framework identifies the optimal islanding strategy using real-time measurements through a multi-stage process:
1. Trajectory Similarity Indexes
Instead of a single metric, the authors define four distinct indexes to compare generator behavior:
- Angle Deviation Similarity: Measures the relative distance between rotor angle trajectories.
- Swing Direction Similarity: Checks if generators are moving in the same general direction.
- Rotating Speed Deviation Similarity: Compares variations in generator speeds.
- Corner Deviation Similarity: Captures the "sharpness" or internal oscillation degree of the trajectories.
2. Entropy Weight Theory
To avoid the bias of manual weighting, the system uses entropy theory to mathematically determine which index provides the most "information" for a specific disturbance. This allows the clustering logic to adapt automatically to the current state of the grid (e.g., prioritizing speed data if speed swings are the dominant feature of a fault).
3. Hierarchical Clustering and Cutset Optimization
An agglomerative (bottom-up) algorithm groups generators with the highest coherency into clusters. Once identified, the system solves a mathematical model to find the "minimal cutset"—the specific lines to disconnect that satisfy coherency constraints while minimizing total active power flow disruption.
Experimental Validation
The scheme was validated using two standard power system benchmarks:
- 16-Generator 68-Bus System: A common test case for medium-scale stability studies.
- Reduced WECC 29-Unit 179-Bus System: A complex model representing the Western Electricity Coordinating Council (North America) grid.
To test robustness, white Gaussian noise was added to the simulated WAMS data, and a median filter was employed to handle measurement errors typical of real-world Phasor Measurement Units (PMUs).
Key Results
Compared to traditional slow-coherency methods, the WAMS-based approach yielded significant improvements:
- Reduced Disruption: In the 68-bus system, the proposed method reduced power flow disruption by 30.3% to 43.1%. In the WECC 179-bus system, disruption was reduced by 46.6%.
- Operational Stability: The method often resulted in fewer, more stable islands (e.g., 2 or 3 islands instead of the 5 suggested by static methods), making the system easier for operators to manage during restoration.
- Dynamic Adaptability: The core advantage is that coherency is treated as a response to a specific event rather than a fixed property of the topology, allowing for islands that make sense for the actual emergency occurring.
Limitations and Future Work
While effective, the method assumes high PMU coverage across the grid. Future research should address the real-time computational latency for extremely large-scale grids (thousands of buses) where the window for islanding is mere milliseconds. Additionally, coordinating this scheme with other automated responses, such as Under-Frequency Load Shedding (UFLS), remains a key area for exploration.
Reference: Lin, Z., Wen, F., Zhao, J., & Xue, Y. (2016). Controlled islanding schemes for interconnected power systems based on coherent generator group identification and wide-area measurements. Journal of Modern Power Systems and Clean Energy, 4(3), 440-453.
Summary updated