Condition Assessment of Power Cable for Incomplete Information Based on Probabilistic Neural Network

Erxia Li, Yonghua Fan, Chaoqun Kang, Yuling Li, Xinrui Hao, Zheng ZhangInternational Journal of Control and Automation 2017 · DOI

Abstract

A new assessment method based on the combination of factor analysis and probabilistic neural network (PNN) is proposed to meet the research of main equipment condition-based maintenance in power distribution network. As the quantity of parameters that represent the state of the cable is many, a multi-source information database is established. Missing parameters for incomplete information are eliminated, and factor analysis is used to calculate the main factors of the database and their factor scores. A probabilistic neural network is then used to evaluate the operation status of the cable. Simulation results show that the proposed method can assess the state of power cable condition for incomplete information effectively and accurately, providing reliable guidance for cable maintenance.

Introduction

Power cables are critical components of the electrical grid, yet monitoring their health is inherently complex. While modern systems can track dozens of parameters—ranging from partial discharge and dielectric loss to various operating temperatures—real-world data collection is often flawed. Sensors fail, communication links drop, and maintenance records are frequently incomplete.

Existing assessment methods, such as fuzzy logic or analytic hierarchy processes, typically struggle with this "incomplete information" problem. These methods often require a full dataset to function or rely heavily on subjective human judgment to fill gaps. This research introduces an automated, scientific framework to evaluate cable health (categorized as Normal, Attention, Abnormal, or Serious) even when the available data is far from perfect.

Methodology

The proposed assessment framework utilizes a two-stage pipeline designed to handle data redundancy and classification.

1. Factor Analysis (FA)

The first stage involves dimensionality reduction using Factor Analysis. Instead of processing 22 individual parameters directly, FA identifies "common influence factors." For instance, partial discharge, insulation resistance, and dielectric loss all provide overlapping information regarding "insulation strength." If one sensor fails, the remaining active sensors can still inform the "main factor" score. This approach allows the system to effectively "eliminate" missing parameters while retaining the core diagnostic information.

2. Probabilistic Neural Network (PNN)

The distilled factor scores are then fed into a Probabilistic Neural Network (PNN). PNNs are radial basis networks optimized for classification tasks using Bayesian decision theory to determine optimal boundaries between health states. They are particularly effective for engineering data due to their high precision and ability to model non-linear relationships without the "black box" opacity of some other AI models.

Flowchart of the proposed power cable condition assessment method.

Data and Experimental Setup

The study utilized a multi-source information database containing 100 groups of historical power cable state data. Each group originally comprised 22 parameters, including equipment specifications (e.g., rated voltage), operational data (e.g., load, age), and inspection data (e.g., sheath resistance, joint temperature).

For the experimental phase, 80 groups were used for training the PNN, while 20 groups were reserved for testing. To evaluate robustness, the researchers simulated "mild" (1–5 missing variables) and "severe" (12 missing variables) information loss by manually removing parameters from the test sets.

Results and Discussion

The core strength of this method lies in leveraging information redundancy. State variables in power systems are highly correlated; for example, ambient temperature, core temperature, and joint temperature all contribute to the latent state of "cable insulation temperature."

Mapping of raw parameters to latent health factors, illustrating information redundancy.

By training the neural network on factor scores rather than raw data, the model becomes decoupled from specific sensor dependencies. Key findings include:

  • Dimensionality Reduction: Factor Analysis successfully compressed 22 variables into just 7 "main factors" while retaining nearly 87% of the original information.
  • High Accuracy: Under "mild" incomplete information (up to 5 missing parameters), the system maintained a 95% accuracy rate.
  • Robustness: Even under "severe" conditions with over 50% data loss (12 parameters missing), the system achieved an 80% accuracy rate.
  • Graceful Degradation: Errors made by the system were typically "adjacent" (e.g., labeling a "Normal" cable as "Attention"), providing a conservative safety margin for maintenance engineers.

Conclusion

The combination of Factor Analysis and Probabilistic Neural Networks provides a robust solution for power cable health assessment under real-world conditions of incomplete data. While the current study is limited by a relatively small dataset of 100 samples, the results demonstrate that latent variable modeling can effectively buffer against sensor failure. Future work will focus on expanding the dataset size to improve generalizability and adapting the framework for real-time streaming assessment in power control centers.

Summary updated

Abstract

A new assessment method based on the combination of factor analysis and probabilistic neural network (PNN) is proposed to meet the research of main equipment condition-based maintenance in power distribution network As the quantity of parameters that represent the state of the cable is manythe multi-source information database is established The missing parameters for incomplete information is eliminatedand the factor analysis is used to calculate the main factors of the database and their factor scores, and the probability neural network was used to evaluate the operation status of the cable, then obtain a condition assessment method of power cable based on the probability neural networkSimulation results show that the proposed method could assess the state of power cable condition for the incomplete information effectively and accurately, and also provide reliable guidance for the cable maintenance.
BibTeX
@article{li2017condition,
  author = {Erxia Li and Yonghua Fan and Chaoqun Kang and Yuling Li and Xinrui Hao and Zheng Zhang},
  title = {{Condition Assessment of Power Cable for Incomplete Information Based on Probabilistic Neural Network}},
  journal = {International Journal of Control and Automation},
  year = {2017},
  doi = {10.14257/ijca.2017.10.9.01},
}
Figure