CD-HOC: Indoor Human Occupancy Counting using Carbon Dioxide Sensor Data

Irvan Bastian Arief Ang, Flora D. Salim, Margaret HamiltonarXiv 2017

TL;DR

This paper introduces CD-HOC, a novel method for accurately counting indoor human occupancy using only a single carbon dioxide (CO2) sensor. By decomposing CO2 data into trend, seasonal, and irregular components and applying a zero-pattern adjustment, CD-HOC achieves significant accuracy improvements over baseline methods in both small rooms and large venues like cinema theaters.

What Problem Does This Paper Address?

Modern Building Management Systems (BMS) rely heavily on understanding human occupancy to optimize energy consumption, particularly for HVAC systems. However, accurately sensing occupancy is challenging, especially in older buildings lacking extensive sensor infrastructure. While image-based methods exist, they raise privacy concerns. Existing sensor-based approaches often require multiple sensor types, increasing cost and complexity. This paper tackles the problem of achieving accurate indoor human occupancy counting using a single, widely available sensor – the CO2 sensor – thereby reducing costs and respecting privacy.

Methods

The core of CD-HOC involves a multi-stage approach:

  • Data Decomposition: The authors employ two variants of seasonal-trend decomposition:
  • STD (Seasonal-Trend Decomposition): A customized version using moving averages to break down CO2 and occupancy data into trend, seasonal, and irregular components.
  • STL (Seasonal-Trend Decomposition based on Loess): A more robust method that uses Loess smoothing for decomposition.
  • Feature Engineering: The decomposed components (trend, seasonal, irregular) are treated as features.
  • Correlation Modeling: Pearson correlation is used to assess the similarity between CO2 and occupancy components. Polynomial M5 linear regression is then applied to model the relationships for each component.
  • Zero Pattern Adjustment (ZPA): A novel technique to improve accuracy by learning vacant room behavior from historical data, specifically addressing false positives during non-occupied periods.
  • Additive Decomposition: The predicted components are recombined using an additive model to reconstruct the final occupancy prediction.

Datasets

The study utilized two distinct datasets:

  • Academic Staff Room: Data collected from a small academic office at RMIT University, Australia, using a Netatmo urban weather station for CO2 readings. Occupancy was manually labeled by a volunteer.
  • Cinema Theatre: Data collected from a cinema theater in Mainz, Germany, using mass spectrometry for CO2 measurements. Occupancy data was derived from ticket sales for movie sessions.

Key Insights and Ideas

  • CO2 as a Sole Predictor: The research demonstrates that a single CO2 sensor, when processed with advanced techniques, can be a surprisingly effective predictor of human occupancy, challenging the need for multiple sensor types.
  • Decomposition is Key: Breaking down the time-series data into trend, seasonal, and irregular components allows for more nuanced modeling of the complex relationship between CO2 and occupancy.
  • Zero Pattern Adjustment for Vacancy: The ZPA method is crucial for improving accuracy by specifically handling periods when a room is vacant, a common challenge in occupancy prediction.
  • Context Matters: The performance of the CD-HOC model, while generally superior, shows variations between the small academic room and the large cinema theater, highlighting the importance of context-specific tuning.

Key Results

  • Academic Staff Room: CD-HOC achieved an average accuracy of 94.68% with zero units error tolerance, outperforming the baseline Support Vector Regression (SVR) by 4.33%. With one unit error tolerance, accuracy reached 99.52%.
  • Cinema Theatre: CD-HOC demonstrated an average 8.46% higher accuracy than SVR. With ten units error tolerance (acceptable for large venues), CDHOC-STD achieved 73.76% accuracy, outperforming SVR's 72.7%.
  • Long-Term Prediction: The model showed good stability, with accuracy reducing to only 6.9% after predicting more than 10 days ahead.

Limitations and Future Work

  • Location-Specific Training: The CD-HOC model needs to be re-trained for each location to achieve optimal accuracy, indicating a lack of universal generalizability without further work.
  • Dataset Size and Availability: The authors note that many previous experiment datasets are not publicly available, hindering direct comparison and replication.
  • Future Work: The authors plan to extend this research to other locations with different environmental dynamics and characteristics. They also aim to explore real-time, on-line learning to further enhance performance.

Summary updated

Abstract

Human occupancy information is crucial for any modern Building Management System (BMS). Implementing pervasive sensing and leveraging Carbon Dioxide data from BMS sensor, we present Carbon Dioxide - Human Occupancy Counter (CD-HOC), a novel way to estimate the number of people within a closed space from a single carbon dioxide sensor. CD-HOC de-noises and pre-processes the carbon dioxide data. We utilise both seasonal-trend decomposition based on Loess and seasonal-trend decomposition with moving average to factorise carbon dioxide data. For each trend, seasonal and irregular component, we model different regression algorithms to predict each respective human occupancy component value. We propose a zero pattern adjustment model to increase the accuracy and finally, we use additive decomposition to reconstruct the prediction value. We run our model in two different locations that have different contexts. The first location is an academic staff room and the second is a cinema theatre. Our results show an average of 4.33% increment in accuracy for the small room with 94.68% indoor human occupancy counting and 8.46% increase for the cinema theatre in comparison to the accuracy of the baseline method, support vector regression.
BibTeX
@misc{ang2017cd,
  author = {Irvan Bastian Arief Ang and Flora D. Salim and Margaret Hamilton},
  title = {{CD-HOC: Indoor Human Occupancy Counting using Carbon Dioxide Sensor Data}},
  year = {2017},
  eprint = {1706.05286},
  archivePrefix = {arXiv},
  url = {https://arxiv.org/abs/1706.05286},
}
Figure