Analysis of Energy Reduction of Free Cooling System with Regions of South Korea

Jung-In Yoon, Chang-Hyo Son, Kwang-Hwan Choi, Seung-Moon Baek, Jeong-Ho Heo, Youngmin KimJournal of the Korean Solar Energy Society 2014

Abstract

This research investigates the energy efficiency of "free cooling" systems—technologies that leverage low outdoor air temperatures to chill water for industrial and IT infrastructure—across diverse climatic zones in South Korea. By simulating annual operations in Seoul, Chuncheon, Daejeon, and Ulsan, the study quantifies regional energy savings. Results indicate that while free cooling can reduce compressor energy consumption by up to 17.5% in colder inland regions like Chuncheon, its effectiveness is more modest (11%) in urban centers like Seoul, emphasizing the critical role of local climate in determining system ROI.

Introduction

Modern high-tech facilities, such as data centers and semiconductor manufacturing plants, generate substantial heat and require continuous, year-round cooling. Traditional refrigeration relies heavily on mechanical compressors, which are major energy consumers. Free cooling presents a sustainable alternative by using a heat exchanger (dry cooler) to dissipate heat into the atmosphere when outdoor temperatures are sufficiently low. However, the practical energy savings of these systems are highly dependent on local meteorological conditions. This study addresses the gap in regional performance data for free cooling systems within South Korea.

Methodology and System Configuration

The researchers modeled a cooling system using Aspen HYSYS 8.0v, incorporating a scroll compressor, a shell-and-tube evaporator, and a dry cooler. The system's operational logic is governed by the outdoor temperature ($T_{out}$):

  1. Isolated Free Cooling ($T_{out} < 2^\circ\text{C}$): The compressor is deactivated, and the dry cooler manages the entire cooling load.
  2. Parallel/Hybrid Operation ($2^\circ\text{C} \leq T_{out} \leq 7^\circ\text{C}$): The dry cooler provides pre-cooling, with the mechanical refrigerator supplying the remaining capacity to meet the target chilled water temperature.
  3. Mechanical Cooling ($T_{out} > 7^\circ\text{C}$): The system relies exclusively on mechanical refrigeration as outdoor air is too warm for effective heat exchange.
Figure 1: Schematic of the free cooling system integrated with a traditional refrigeration cycle.

The simulation utilized hourly temperature data from 2013 for four representative cities: Seoul (urban), Chuncheon (cold inland), Daejeon (central), and Ulsan (coastal industrial).

Regional Performance and Key Results

The study's primary metric was the reduction in annual compressor work compared to a conventional refrigeration-only system. The results demonstrated significant regional variation:

  • Chuncheon: Achieved the highest energy reduction at 17.5%. Its colder climate allowed for extended periods of "zero-power" cooling, particularly in January and February.
  • Daejeon: Recorded a 15% reduction.
  • Ulsan: Achieved a 14% reduction.
  • Seoul: Showed the lowest reduction at 11%.
Figure 4: Comparison of monthly compressor work between the existing system and the free cooling system across four South Korean cities.

Interestingly, although Seoul is located further north than Ulsan, it exhibited lower energy savings. This suggests that local microclimates and specific hourly temperature distributions are more influential than latitude alone. The data confirms a hard performance ceiling at 7°C; once outdoor temperatures exceed this threshold, the free cooling component loses all utility for standard 7°C chilled water supplies.

Conclusion and Future Outlook

This analysis proves that free cooling is a viable energy-saving strategy for South Korean infrastructure, though its benefits are geographically sensitive. Chuncheon emerges as the most favorable location for implementation among the studied cities.

Limitations of this study include the reliance on a single year of weather data (2013) and the assumption of a fixed cooling load (28,000 kcal/h). Future research should incorporate multi-year climate averages to account for increasing weather volatility and explore the performance of "wet" cooling towers, which may offer enhanced cooling potential compared to the dry coolers evaluated here.

Summary updated

Abstract

e m wi t hRe g i o n so fSo u t hKo r e a 윤정인
BibTeX
@article{yoon2014analysis,
  author = {Jung-In Yoon and Chang-Hyo Son and Kwang-Hwan Choi and Seung-Moon Baek and Jeong-Ho Heo and Youngmin Kim},
  title = {{Analysis of Energy Reduction of Free Cooling System with Regions of South Korea}},
  journal = {Journal of the Korean Solar Energy Society},
  year = {2014},
  doi = {10.7836/kses.2014.34.3.082},
}
Figure