NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Analysis of Data From Single-Row Heat Exchanger Experiments Using an Artificial Neural Network

Gerardo Dı́az, José Pedro Monteagudo Yanes, Mihir Sen, K. T. Yang, Rodney L. McClainFluids 1996

Abstract

Abstract Experimental data obtained from tests relating to two different single-row heat exchangers are analyzed by means of an artificial neural network. The experiments are carried out by using hot water and room-temperature air as the rn-tube and over-tube fluids, respectively. The two heat exchangers are similar in the air side but with different water-side circuiting. The data obtained consisted of values for the flow rates, the inlet temperatures, and outlet temperatures for both fluids. Data analysis was through a neural network program written using the generalized-delta back-propagation algorithm. Through a random selection process, 75% of the experimental runs are chosen for training and 25% for testing. Flow rates and the inlet temperatures for both water and air are used as the input data for the neural network, and the heat transfer rates are the output. Once the neural network was trained, the values of the heat transfer rates for the test data are predicted. The predictions are compared with the actual measurements, and with the results of a linear interpolation procedure.
BibTeX
@inproceedings{daz1996analysis,
  author = {Gerardo Dı́az and José Pedro Monteagudo Yanes and Mihir Sen and K. T. Yang and Rodney L. McClain},
  title = {{Analysis of Data From Single-Row Heat Exchanger Experiments Using an Artificial Neural Network}},
  booktitle = {Fluids},
  year = {1996},
  doi = {10.1115/imece1996-0953},
}

Loading related content...