An improved hybrid multilevel converter for renewable energy generation

Pengfei Hu, Xinwei Sun, Xi Wang, Lun Tang, Wei Tang2016 · DOI

TL;DR

This paper introduces an improved hybrid multilevel converter (HMC) designed to tackle the challenges of integrating renewable energy sources into the power grid via High Voltage Direct Current (HVDC) transmission. The proposed HMC topology combines the strengths of thyristor-based current source converters (CSCs) and IGBT-based voltage source converters (VSCs), offering high voltage capability and efficient power control, even during DC fault conditions.

What Problem Does This Paper Address?

The increasing integration of renewable energy sources like wind and solar power presents a significant challenge for grid stability and efficiency. High Voltage Direct Current (HVDC) transmission is a promising solution for this integration, with converters being the critical component. Traditional converters, such as Current Source Converters (CSCs) and Voltage Source Converters (VSCs), have inherent limitations. CSCs, while offering high voltage withstand and low losses, suffer from commutation failures, large harmonics, and inflexible power control. VSCs, on the other hand, provide excellent output quality with fewer harmonics but have lower voltage withstand capabilities, higher losses, and cannot handle DC current failures. This paper addresses the need for a converter that can combine the advantages of both, specifically by offering high voltage capability, efficient power control, and robustness against DC fault conditions.

Methods

The paper proposes an "improved hybrid multilevel converter" (HMC) topology. This HMC is built upon cascaded H-bridges (CHBs) and direction switches (DS) composed of thyristors with anti-parallel diodes. Each phase of the converter consists of two arms, each comprising a DS and a CHB. The CHB itself is made up of multiple sub-modules (SMs), each capable of four states: positively inserted, negatively inserted, bypassed, or blocked, allowing for precise voltage control.

For modulation, the paper adopts the Nearest Level Modulation (NLM) strategy, which is well-suited for CHBs with a large number of H-bridges. To ensure voltage balance across the individual H-bridges, a voltage balancing algorithm is implemented. For control, the paper proposes an active and reactive power decouple control strategy for normal operation. Crucially, it also outlines a control strategy that allows the HMC to function as a STATCOM (Static Synchronous Compensator) during DC fault conditions, enhancing its resilience.

Datasets

Not discussed in the paper. The paper relies on simulations using PSCAD/EMTDC for validation.

Key Insights and Ideas

  • Hybrid Topology Advantage: The core idea is to leverage the strengths of both CSCs (high voltage, low loss) and VSCs (low harmonics, good control) in a single converter. This hybrid approach aims to overcome the individual limitations of each.
  • Robustness to DC Faults: A significant contribution is the proposed ability of the HMC to transition to a STATCOM-like operation during DC faults. This "ride-through" capability is crucial for grid stability when integrating renewables, as DC faults can be disruptive.
  • NLM for Scalability: The adoption of Nearest Level Modulation is a practical choice for multilevel converters with a large number of sub-modules, simplifying the control and ensuring efficient voltage shaping.
  • Voltage Balancing is Key: For multilevel converters, ensuring that the voltage is evenly distributed across all sub-modules is critical for reliable operation and preventing component stress. The paper highlights the importance of a dedicated voltage balancing algorithm.

Key Results

The paper presents simulation results in PSCAD/EMTDC to validate the proposed topology, modulation, and control strategies.

  • Normal Operation: Figure 6(a) shows that the HMC performs excellently under normal operating conditions, with stable output voltage and current waveforms, and controlled active and reactive power.
  • DC Fault Condition: Figure 6(b) demonstrates the HMC's ability to handle a DC fault. The simulation shows that the converter can maintain stable operation and manage power flow even when a fault occurs, effectively acting as a STATCOM. The output performance is described as "excellent" during this condition.

Limitations and Future Work

  • Limitations: The paper focuses on a single-phase equivalent circuit for mathematical modeling and presents simulation results. While the simulations are extensive (61 voltage levels), real-world implementation complexities and experimental validation are not detailed. The paper also mentions "unknown" states for SMs depending on current direction, which might imply areas for further refinement in control.
  • Future Work: The paper's conclusion suggests that the proposed topology and control strategies are validated by simulations. Future work would naturally involve experimental validation and potentially exploring further optimizations for efficiency and cost-effectiveness in large-scale renewable energy integration systems. The transition to STATCOM mode during faults is a key area that could be further explored in terms of its dynamic response and effectiveness under various fault scenarios.

Summary updated

Abstract

With the development of renewable energy (i.e. wind power and solar power) generation, its integration to the power grid has becoming a more and more important challenge. High voltage direct current (HVDC) transmission [1-2] is a suitable scheme for the integration. The key unit of HVDC is the converter. In general, there are two types of converters classified by the electronic devices. The one is named the current source converter (CSC) based on thyristors. The other one is named the voltage source converter (VSC) [3-4] based on insulated-gate bipolar transistors (IGBTs). The disadvantages of CSC are the probability of commutation failure, large harmonics, and inflexibility of power control. The advantages of CSC are high withstanding voltages and few losses. On the contrary, VSC has few harmonics and excellent output, but it has lower withstanding voltages and higher losses. And VSC cannot deal with direct current failure. To combine advantages of both topologies, an improved hybrid multilevel converter (HMC) is presented in this paper.
BibTeX
@misc{hu2016improved,
  author = {Pengfei Hu and Xinwei Sun and Xi Wang and Lun Tang and Wei Tang},
  title = {{An improved hybrid multilevel converter for renewable energy generation}},
  year = {2016},
  doi = {10.2991/nceece-15.2016.241},
}
Figure