Abstract
To effectively enhance the integration of distributed and renewable energy sources in future smart microgrids, economical energy management accounting for the principal challenge of the variable and non-dispatchable renewables is indispensable and of significant importance. Day-ahead economic generation dispatch with demand-side management for a microgrid in islanded mode is considered in this paper. With the goal of limiting the risk of the loss-of-load probability, a joint chance constrained optimization problem is formulated for the optimal multi-period energy scheduling with multiple wind farms. Bypassing the intractable spatio-temporal joint distribution of the wind power generation, a primal-dual approach is used to obtain a suboptimal solution efficiently. The method is based on first-order optimality conditions and successive approximation of the probabilistic constraint by generation of p-efficient points. Numerical results are reported to corroborate the merits of this approach.
Introduction
As global energy systems transition toward decentralized "smart grids," microgrids—localized energy clusters capable of operating independently from the main utility grid—have become a critical infrastructure component. However, when operating in "islanded mode," these systems face a significant reliability challenge: they cannot rely on the external grid to compensate for the inherent variability of renewable sources like wind power.
The core technical challenge is Economic Dispatch (ED), which involves determining the optimal power output for each generator and energy storage unit to meet demand at minimum cost. Introducing wind power transforms this into a joint chance-constrained optimization problem. These problems are notoriously difficult to solve because the probability of wind failure across multiple locations and time intervals creates a non-convex, "jagged" mathematical landscape that traditional solvers struggle to navigate efficiently.
Methodology
This paper proposes a novel Primal-Dual Approach to bypass the complexity of joint probability distributions. The methodology is built upon three pillars:
- p-efficient Points: Instead of modeling every possible wind scenario, the algorithm identifies specific "efficient" points on the boundary of the probability distribution. These points represent the minimum wind levels required to meet a specific reliability target (e.g., a 95% confidence level).
- Convexification: To handle the non-convex nature of the original problem, the authors use a convex combination of these $p$-efficient points to approximate a "safe zone" for microgrid operations.
- Iterative Master-Slave Setup: A Master Problem solves the economic dispatch based on current safe points, while a Subproblem (a mixed-integer program) searches for new $p$-efficient points to further optimize the solution.
This framework also incorporates Demand-Side Management (DSM), allowing the system to shift flexible loads—such as electric vehicles or industrial processes—to periods of high wind availability.
Results and Discussion
The proposed method was evaluated in a simulated microgrid environment featuring three conventional generators, six dispatchable loads, three energy storage units, and four wind farms. Wind data was modeled using a two-parameter Weibull distribution, accounting for both temporal and spatial correlations.
Cost and Reliability Trade-offs
Numerical results demonstrate that the primal-dual approach significantly outperforms traditional Scenario Approximation (SAA) methods. For a 95% reliability target ($p=0.95$) with 1,000 samples, the proposed method achieved an optimal cost of $68.82**, compared to **$82.84 for SAA. Furthermore, the method exhibits high stability regarding sample size; as shown in the cost analysis, increasing the number of Monte Carlo samples ($N_s$) beyond a certain point yields diminishing returns in accuracy, suggesting the method is robust even with limited data.
Peak Shaving and Load Flexibility
A key insight from the study is the role of energy storage and DSM in "peak shaving." The scheduling results indicate that energy storage units successfully charge during low-demand periods (e.g., 4 PM–7 PM) and discharge during peak hours. Simultaneously, dispatchable loads are shifted to later hours (9 PM–12 AM) to smooth the overall power profile, reducing the need for expensive conventional backup generation.
Conclusion
The proposed primal-dual approach offers a computationally efficient and cost-effective solution for managing the uncertainties of renewable-heavy microgrids. By utilizing $p$-efficient points, the system maintains high reliability without the excessive conservatism of traditional worst-case scenario modeling. Future research will focus on incorporating high-speed stability constraints, such as frequency and voltage regulation, and more sophisticated battery degradation models to further refine the long-term economic viability of islanded microgrids.