Algorithm of Differential-protection on Rectifier Valve Group of the Electrolytic Aluminum Rectification System

Xiaodong Zhao, Ya Zhang, Bei Tian, Xutao Li, Di Zhang, Zhiguo Hao2018

Abstract

The rectifier group is an important equipment for the electrolytic aluminum rectification system. The valve short circuit and valve breakdown failure, which would cause serious accidents, often happened. The sensitivity of the existing arc protection action is affected by the fault position, and the equipment burning accident, caused by the failure to detect in time, happened frequently. This paper derived the AC/DC differential protection algorithm of the rectifier group which was based on the structure of the rectifier group and conceived from the idea of "valve short circuit protection". The simulation results showed that the algorithm can identify the fault, which occurred inside, quickly and accurately. This algorithm provides a new method for the protection of the rectifier valve group, which fills the gap of the differential protection of the rectifier valve group.

Introduction

In the electrolytic aluminum industry, rectifier valve groups are the critical components that convert high-voltage AC into the massive direct currents required for production. However, these components are highly susceptible to "valve short circuits" and breakdowns. Existing protection schemes, such as arc protection, suffer from significant flaws: they are often slow (taking 300–500ms to act) and their sensitivity is heavily dependent on the physical location of the fault. In high-power environments, such delays can lead to catastrophic equipment explosions or irreparable damage. This paper introduces a novel AC/DC differential protection algorithm designed to fill this gap by providing high-speed, localized detection of internal faults.

Methodology

The researchers developed an AC/DC Differential Protection Algorithm based on the principle of "valve short circuit protection," typically used in HVDC transmission but adapted here for the parallel bridge structures common in industrial electrolysis.

The system architecture showing the voltage regulating transformer, phase-shifting transformer, and the complex rectifier valve group.

Algorithm Logic

The core of the approach is Instantaneous Current Analysis. Under normal operating conditions, the absolute maximum value of the three-phase AC current should correlate directly with the DC side current. Since a rectifier valve group in this context consists of four three-phase bridges in parallel, the authors derived a mathematical formula to sum the positive instantaneous currents from all AC branches.

To ensure the system does not trigger on measurement noise or minor imbalances, a Ratio Differential Criterion was implemented. The protection only activates if the difference between the calculated AC-sum and the actual DC-out (the operating current, $I_{op}$) exceeds a dynamic threshold relative to the restraint current ($I_{res}$).

The ratio differential protection characteristic curve defining the 'action area' for fault detection.

Validation

The algorithm was validated using a PSCAD simulation model of a ZHSPTB-117000/330 type rectifier transformer. The researchers simulated five internal "intra-regional" failures (such as diode shorts and DC bus shorts) and three "out-of-zone" external faults to test both sensitivity and stability.

Key Results and Insights

The simulation results demonstrated that the algorithm meets the critical 5ms detection benchmark. This speed is essential to prevent converter diodes from burning out, a failure that can lead to months of maintenance.

  • High Sensitivity: In diode short circuit tests, the "Differential Current" (70.75) was nearly seven times higher than the "Action Value" (10.63), indicating a robust safety margin for detection.
  • Selectivity and Stability: For external faults occurring outside the valve group, the differential current remained at zero. This proves the algorithm is highly selective and will not cause "false trips" during outside disturbances.
  • System Integration: By adding this valve-group-specific algorithm, engineers can create a comprehensive "whole unit" protection scheme that covers the voltage regulator, phase-shifting transformer, and rectifier cabinet as a single, secure interval.

Conclusion

This novel AC/DC differential protection algorithm provides a significant advancement in the safety of electrolytic aluminum rectification systems. By utilizing instantaneous values and a ratio differential criterion, it achieves the necessary speed to prevent catastrophic hardware failure. Future work should focus on real-world hardware implementation, addressing factors such as sensor synchronization and the harsh electromagnetic environment of aluminum plants, as well as optimizing parameter tuning for specific high-capacity industrial settings.

Summary updated

Abstract

The rectifier group is an important equipment for the electrolytic aluminum rectification system. The valve short circuit and valve breakdown failure, which would cause serious accidents, often happened. The sensitivity of the existing arc protection action is affected by the fault position, and the equipment burning accident, caused by the failure to detect in time, happened frequently. This paper derived the AC/DC differential protection algorithm of the rectifier group which was based on the structure of the rectifier group and conceived from the idea of "valve short circuit protection". The simulation results showed that the algorithm can identify the fault, which occurred inside, quickly and accurately. This algorithm provides a new method for the protection of the rectifier valve group, which fills the gap of the differential protection of the rectifier valve group.
BibTeX
@misc{zhao2018algorithm,
  author = {Xiaodong Zhao and Ya Zhang and Bei Tian and Xutao Li and Di Zhang and Zhiguo Hao},
  title = {{Algorithm of Differential-protection on Rectifier Valve Group of the Electrolytic Aluminum Rectification System}},
  year = {2018},
  doi = {10.2991/ecae-17.2018.25},
}
Figure