Abstract
The AKTIVA project investigates the potential of unglazed solar collectors to serve as a multi-functional building "skin." By acting as a heat source for heat pumps during winter and a radiative cooler at night during summer, these systems offer a circular approach to thermal management. Validated simulations in Swiss climates (Zurich and Lugano) show that this integrated system can cover up to 90% of cooling demand and 75% of heating demand, significantly lowering the carbon footprint of office buildings.
The Challenge of Modern Building Efficiency
Modern buildings with high-performance insulation (low U-values) are highly efficient at retaining heat, which is beneficial in winter but often leads to overheating in summer. This is particularly true for office environments with high internal heat gains from equipment and occupants. While active air conditioning is the standard solution, it is energy-intensive and contributes to peak electricity demand.
The AKTIVA researchers address this by asking: Can we optimize the building’s outer surface to provide "free cooling" via night-time radiation and convection, while still serving as an efficient heat source for a heat pump during the winter?
System Design and Integration
The study employed a three-tier approach: laboratory testing of unglazed collectors with varying selective coatings, Matlab-Simulink modeling using the CARNOT Toolbox, and full system integration. The system relies on Thermally Activated Building Systems (TABS)—pipes embedded in concrete slabs—that allow for low-temperature heating and high-temperature cooling, making the modest temperature differences provided by the collectors highly effective.
Key Results and Performance
Simulations using standardized Swiss weather data (Zurich average and Lugano warm years) revealed high performance across different configurations. In Zurich, "free cooling" (night-time radiation/convection) covered up to 90% of the cooling load. In the warmer Lugano climate, utilizing the source storage as a "cold buffer" during the day significantly improved system resilience, increasing cooling coverage by an additional 10%.
Key Insights
- Radiative Cooling Potential: At night, an unglazed surface with high emissivity (ε = 0.9) effectively "dumps" heat into the cold sink of outer space via long-wave radiation.
- The Selectivity Trade-off: While high emissivity is excellent for summer cooling, it can slightly penalize winter heat absorption. However, the study found this penalty to be minor compared to the massive gains in summer cooling potential.
- Efficiency: The system achieved a Seasonal Performance Factor (SPF) of approximately 4.0 to 5.0, meaning for every 1 unit of electricity used, up to 5 units of thermal energy were delivered.
Limitations and Future Work
In extreme weather, the heat pump might reach its lower operating temperature limit, requiring a secondary backup. Future work will focus on control optimization—using smart logic to decide exactly when to charge the storage or bypass it to maximize seasonal efficiency. Additionally, the direct use of these surfaces for Domestic Hot Water (DHW) in transitional seasons remains an area for further exploration.
Summary updated