A Single-Phase High-Impedance Ground Faulty Feeder Detection Method for Small Resistance to Ground Systems Based on Current-Voltage Phase Difference

Zequan Hou, Zhihua Zhang, Yizhao Wang, Jiandong Duan, Wanying Yan, Wenchao Lu2022

TL;DR

This paper introduces a novel method for detecting single-phase high-impedance ground faults (SPHIF) in small resistance to ground systems (SRGS). By analyzing the phase difference between zero-sequence current and the faulty phase voltage, the method offers improved sensitivity and reliability compared to traditional approaches, even under challenging conditions like high transition resistance and noise.

What Problem Does This Paper Address?

Modern urban distribution networks are increasingly using small resistance to ground systems (SRGS) due to their operational advantages. However, these systems are vulnerable to single-phase high-impedance ground faults (SPHIF), where the fault resistance is significant (e.g., due to contact with trees, asphalt, or human bodies). Traditional protection methods, like fixed-time zero-sequence overcurrent protection, struggle to detect these faults when the transition resistance exceeds approximately 100 Ω. This limitation poses a significant safety risk, as SPHIFs account for a notable percentage of ground faults in distribution networks. Existing advanced methods often rely on difficult-to-measure signals like neutral zero-sequence current or busbar zero-sequence voltage, or require extensive data and complex calibration, limiting their practical applicability.

Methods

The proposed method leverages the Current-Voltage Phase Difference (CVPD) to detect SPHIFs. The core idea is to analyze the phase relationship between the zero-sequence current (ZSC) of each feeder and the phase voltage of the faulted phase.

Here's a breakdown of the approach:

  1. Faulty Phase Identification: The method first identifies the faulted phase by examining the RMS values of the three-phase voltages. The phase with the smallest RMS voltage is declared the faulty phase. This is a crucial step as the faulty phase voltage is expected to be the smallest.
  2. Reference Phase Determination: The initial phase of the identified faulty phase voltage is used as a reference. This is a key innovation, as it utilizes an easily measurable signal.
  3. CVPD Calculation: For each feeder, the phase difference between its ZSC and the reference faulty phase voltage is calculated.
  4. Faulty Feeder Detection: A feeder is identified as faulty if its calculated CVPD falls within a specific range (approximately 0° to 20°). Healthy feeders, in contrast, exhibit a phase difference of around -90° to -110°.
  5. Extended Detection Criterion: To enhance robustness against noise and system parameter variations, an extended criterion is proposed, dividing the phase plane into regions for healthy and faulty feeders.

The method is designed to be simple, requiring only readily available measurements like phase voltages and feeder ZSCs, without the need for additional measurement or communication devices.

Datasets

The paper does not explicitly mention or use pre-existing datasets. Instead, it relies on extensive simulations conducted using the PSCAD software. The simulation model is built based on a 10 kV SRGS with specific electrical parameters for feeders (resistance, inductance, capacitance) and grid structure, as detailed in Tables 1 and 2. The simulations are designed to test the method under various fault conditions, including different transition resistances, fault locations, initial phase angles, system scales, noise levels, and data missing ratios.

Key Insights and Ideas

  • Leveraging Phase Difference: The core insight is that the phase relationship between ZSC and faulty phase voltage provides a robust indicator of SPHIF, largely independent of the fault resistance magnitude.
  • Faulty Phase Voltage as Reference: Using the easily measurable initial phase of the faulty phase voltage as a reference is a practical and effective approach, simplifying implementation.
  • Distinguishing Healthy vs. Faulty: The significant phase difference (around 180-200° ahead for faulty vs. 90° ahead for healthy feeders relative to bus ZSV, and then further refined relative to faulty phase voltage) between healthy and faulty feeder ZSCs is the fundamental principle for discrimination.
  • Robustness to Challenges: The method demonstrates remarkable resilience to high transition resistances (up to 5000 Ω), noise interference (-1 dB), and data missing (up to 40%), highlighting its practical utility.

Key Results

The proposed CVPD method demonstrated strong performance across various simulated scenarios:

  • High Transition Resistance: Successfully detected faults with transition resistances up to 5000 Ω, significantly outperforming traditional methods.
  • Noise Immunity: Showed good interference immunity, reliably detecting faults under -1 dB noise levels.
  • Data Missing Tolerance: Maintained reliability even with up to 40% data missing.
  • Insensitivity to Other Factors: The method was found to be unaffected by different fault locations, initial phase angles, and feeder lengths.
  • Sensitivity and Reliability: The paper claims the method has good sensitivity and reliability, with a reliable and sensitive threshold range.

Limitations and Future Work

  • Faulty Phase Detection Prerequisite: The paper acknowledges that the accuracy of the method relies on correctly identifying the faulty phase. The current method uses a voltage magnitude comparison, which might have a risk of incorrect detection due to the small voltage difference (tens of volts) between phases during SPHIF.
  • Cable Screen Earthing Current: The influence of cable screen earthing current, which exists in actual project cable lines, was not studied and is suggested for future research.
  • Proprietary ZSC Transformer: The paper suggests that using a proprietary ZSC transformer might be beneficial to ensure the sensitivity of the method, implying a potential limitation with standard transformers.

Summary updated