Abstract
Existing liability division methods for harmonic pollution are often inexplicit or physically incomplete. To address these deficiencies, this paper proposes two new methods based on line-transferred power components. By representing harmonic sources as ideal equivalent current sources, the line-transferred power component for each source is determined under the action of all sources. Liability is then divided using two metrics: the ratio of the source's line-transferred active power component to total power (P-method), and the projection of the complex power component (S-method). Simulation results demonstrate that the P-method, based on active power, is the most effective and physically meaningful approach.
Introduction
As modern power grids increasingly integrate power electronic devices, harmonic pollution—distortions in the standard AC waveform—has become a significant concern. These harmonics degrade power quality, damage sensitive equipment, and increase energy losses. To manage this, grid operators must fairly assign liability to specific pollution sources. However, determining the exact contribution of a single source in a multi-source environment is mathematically complex because power does not obey the superposition theorem, unlike voltage and current.
Methodology
The proposed approach overcomes the limitations of traditional voltage-based (V-method) or current-based (I-method) metrics by leveraging the theory of line-transferred power components.
- Source Modeling: Harmonic sources are modeled as ideal equivalent current sources. The system calculates baseline voltage and current components for each source as if it were acting in isolation.
- Power Component Calculation: Using circuit-law formulas, the "line-transferred complex power component" is calculated for each source while all sources act simultaneously. This isolates a single source's contribution to the total power flow.
- Liability Metrics: Two new metrics are introduced:
- P-method (Active Power): Liability is the ratio of a source's line-transferred active power component to the total line-transferred active power.
- S-method (Complex Power): Liability is the ratio of the projection of a source's complex power component onto the total complex power.
Experimental Setup
The authors evaluated these methods using a simulated IEEE 6-bus system, a standard benchmark in power systems engineering. Three harmonic sources (H2, H3, and H5) were introduced at specific buses to observe how different methods apportioned liability across the transmission lines.
Key Results and Discussion
The simulation revealed stark differences in the stability and fairness of the various methods:
- I-method (Current): This method failed significantly, yielding extreme liability ranges. For source H3, liability ranged from -58.68% to 176.64% depending on the line, with a massive standard deviation (0.885).
- V-method (Voltage): This approach was overly compressed, yielding a narrow range (18.6% to 42.0%) that failed to adequately differentiate between the impacts of different sources.
- P-method and S-method: Both proposed methods provided moderate, reasonable ranges. The P-method for H3 ranged from -10.0% to 106.9% with a standard deviation of 0.437.
Active power (P-method) is identified as the most physically meaningful metric because it represents the actual energy delivered. While the S-method is mathematically sound, it is less explicit because it mixes real and reactive power in its projection.
Conclusion
The study concludes that relying solely on voltage or current for harmonic liability is insufficient and often misleading. The proposed P-method, based on line-transferred active power components, provides a stable, fair, and physically grounded framework for quantifying harmonic pollution. It is recommended as the ideal approach for quantitative harmonic management in modern power grids.