A Liability Division Method for Harmonic Pollution Based on Line-Transferred Power Components

Jianchun Peng, Jun Zhou, H. JiangJournal of Power and Energy Engineering 2015

Abstract

Existing liability division methods for harmonic pollution are often inexplicit or physically incomplete. To address these deficiencies, this paper proposes two new methods based on line-transferred power components. By representing harmonic sources as ideal equivalent current sources, the line-transferred power component for each source is determined under the action of all sources. Liability is then divided using two metrics: the ratio of the source's line-transferred active power component to total power (P-method), and the projection of the complex power component (S-method). Simulation results demonstrate that the P-method, based on active power, is the most effective and physically meaningful approach.

Introduction

As modern power grids increasingly integrate power electronic devices, harmonic pollution—distortions in the standard AC waveform—has become a significant concern. These harmonics degrade power quality, damage sensitive equipment, and increase energy losses. To manage this, grid operators must fairly assign liability to specific pollution sources. However, determining the exact contribution of a single source in a multi-source environment is mathematically complex because power does not obey the superposition theorem, unlike voltage and current.

Methodology

The proposed approach overcomes the limitations of traditional voltage-based (V-method) or current-based (I-method) metrics by leveraging the theory of line-transferred power components.

Schematic of line-transferred power components at the Point of Common Coupling (PCC).
  1. Source Modeling: Harmonic sources are modeled as ideal equivalent current sources. The system calculates baseline voltage and current components for each source as if it were acting in isolation.
  2. Power Component Calculation: Using circuit-law formulas, the "line-transferred complex power component" is calculated for each source while all sources act simultaneously. This isolates a single source's contribution to the total power flow.
  3. Liability Metrics: Two new metrics are introduced:
  4. P-method (Active Power): Liability is the ratio of a source's line-transferred active power component to the total line-transferred active power.
  5. S-method (Complex Power): Liability is the ratio of the projection of a source's complex power component onto the total complex power.

Experimental Setup

The authors evaluated these methods using a simulated IEEE 6-bus system, a standard benchmark in power systems engineering. Three harmonic sources (H2, H3, and H5) were introduced at specific buses to observe how different methods apportioned liability across the transmission lines.

The IEEE 6-bus system used for simulation, featuring three harmonic sources (H2, H3, H5).

Key Results and Discussion

The simulation revealed stark differences in the stability and fairness of the various methods:

  • I-method (Current): This method failed significantly, yielding extreme liability ranges. For source H3, liability ranged from -58.68% to 176.64% depending on the line, with a massive standard deviation (0.885).
  • V-method (Voltage): This approach was overly compressed, yielding a narrow range (18.6% to 42.0%) that failed to adequately differentiate between the impacts of different sources.
  • P-method and S-method: Both proposed methods provided moderate, reasonable ranges. The P-method for H3 ranged from -10.0% to 106.9% with a standard deviation of 0.437.

Active power (P-method) is identified as the most physically meaningful metric because it represents the actual energy delivered. While the S-method is mathematically sound, it is less explicit because it mixes real and reactive power in its projection.

Conclusion

The study concludes that relying solely on voltage or current for harmonic liability is insufficient and often misleading. The proposed P-method, based on line-transferred active power components, provides a stable, fair, and physically grounded framework for quantifying harmonic pollution. It is recommended as the ideal approach for quantitative harmonic management in modern power grids.

Summary updated

Abstract

The existing liability division methods for harmonic pollution are either inexplicit or incomplete in physical meaning. To compensate these defects, two new methods are proposed based on line-transferred power components in this paper. At first, all harmonic sources are represented by ideal equivalent current source, line current components and bus voltage components of a source are determined by stimulation of this source with all other sources disabled. Then, the line-transferred power component owing to a source under all sources action together is determined by the theory of line-transferred power components, and called source's line-transferred power component. At last, the liability of a source for line-end harmonic pollution is divided by two methods: the ration of the source's line-transferred active power component to the total line-transferred power, and the ration of projection of the source's line-transferred complex power component to absolute value of the total line-transferred complex power. These two methods are taken into account not only harmonic voltage but also harmonic current in the liability division. Simulation results show that the proposed liability division method based on active power component is the most effective and ideal one.