TL;DR
This paper introduces a novel deep learning approach using a modified MobileNetV4 (MNv4) architecture to accurately identify transformer inrush currents in modern power systems. By fusing multi-source electrical data (voltage, current, and differential current), this method overcomes the limitations of traditional techniques, offering improved reliability and efficiency for transformer protection.
What Problem Does This Paper Address?
Modern power grids are increasingly integrating renewable energy sources, leading to complex harmonic conditions. Traditional methods for identifying transformer inrush currents, which rely on detecting second harmonic components, struggle in these environments. Power electronic converters used in renewable energy systems, particularly during low-voltage ride-through (LVRT) events, introduce significant second harmonics that can cause these traditional methods to misidentify faults. This can lead to incorrect tripping or failure to trip, compromising the stability and security of the power system. The paper aims to develop a more robust and adaptable inrush current identification method that can handle these complex harmonic scenarios.
Methods
The core of this research is a novel identification scheme based on a modified MobileNetV4 (MNv4) architecture. MNv4 is chosen for its efficiency and suitability for resource-constrained embedded systems, common in power protection devices. The method utilizes a multi-source electrical quantity fusion approach, incorporating three-phase voltage, three-phase current, and differential current as input features. This combination addresses the limitations of traditional methods that rely on single features. The MNv4 model is trained and evaluated on a dataset constructed from both PSCAD simulations and real-world engineering field data.
Datasets
The study utilizes a dataset of 3040 samples, comprising 1680 inrush and 1360 non-inrush cases. This dataset was generated using PSCAD electromagnetic transient simulations, covering various scenarios including no-load switching, voltage recovery after fault clearance, coupled inrush phenomena in series/parallel transformer configurations, and internal/external faults. The data was supplemented with field-recorded data and stored in COMTRADE format, with binary labeling (0 for steady-state/normal fault, 1 for inrush condition). A stratified 5:2:3 ratio was used for training, validation, and testing.
Key Insights and Ideas
- Multi-source data fusion is crucial: Relying on a single electrical quantity (like current) is insufficient for accurate inrush current identification in modern, complex power systems. Combining voltage, current, and differential current provides a more comprehensive picture.
- Deep learning excels in complex environments: Traditional methods struggle with the high harmonic content introduced by power electronics. Deep learning models like MNv4 can learn intricate patterns from this complex data.
- Efficiency matters for deployment: For practical application in power protection devices, models need to be computationally efficient. MNv4's architecture offers a good balance between accuracy and resource requirements.
- MNv4's adaptability: The Universal Inverted Bottleneck (UIB) module in MNv4 allows it to dynamically adapt between local convolution and global attention, making it suitable for processing time-frequency characteristics of inrush currents.
Key Results
The proposed MNv4-based method achieved competitive performance in terms of accuracy and recall. Specifically, the MNv4 model demonstrated a high accuracy of 0.997, precision of 0.997, recall of 0.997, and an F1-score of 0.997. This performance is comparable to or better than other evaluated machine learning models, including DTW-kNN, MLP, t-LeNet, FCN, TCN, and ResNet. Notably, MNv4 exhibited superior computational efficiency, converging in just over ten epochs, significantly faster than other deep learning models like t-LeNet which required around 250 epochs. The optimized MNv4-Light architecture further reduced parameters while maintaining high performance.
Limitations and Future Work
The paper acknowledges that while the proposed method significantly improves upon traditional techniques, challenges remain in achieving perfect generalization across all possible scenarios. The authors suggest that future work could focus on further optimizing the model for even greater efficiency and exploring its application in more diverse and complex power system configurations. Additionally, continued research into real-world deployment challenges and validation with larger, more varied datasets would be beneficial.