A DC continuous commutation failure suppression method considering reactive power compensation
Abstract
To address the severity of continuous commutation failure in ultra-high voltage direct current (UHVDC) system and the limitations of existing emergency control methods, this paper proposes a coordinated control strategy integrating synchronous condenser strong excitation and the DC power rapid reduction. Leveraging the characteristics of mechanism of continuous commutation failure is analyzed. Leveraging the characteristics of synchronous condenser, the spontaneous reactive response are used to suppress continuous commutation failure. The DC power rapid reduction control method is employed to compensate for the insufficient response time. And a coordinated continuous commutation failure emergency control method is proposed. Simulation results of the UHVDC transmission system demonstrate that the proposed control method can effectively reduce voltage fluctuations and suppress continuous commutation failure.
BibTeX
@misc{yan2025dc,
author = {Chenyu Yan and Yi Lu and Guopeng Zhu and Yanping Li and Mu Li and Xinyi Zhang and Tao Jia and Shuai Liu and Yanjie Zhang},
title = {{A DC continuous commutation failure suppression method considering reactive power compensation}},
year = {2025},
doi = {10.1109/iceeps66790.2025.11239620},
}Ask Althea to put this paper to the test.