A Configuration Method for Synchronous Condensers Driven by Full Electromagnetic Transient Simulation

Rui Fu, Yingmin Zhang, Wei Wei, Xinwei Sun, Baohong LiElectronics 2025 · DOI

TL;DR

This paper introduces a novel method for optimally placing and sizing synchronous condensers (SCs) in power grids to enhance transient voltage stability, especially in areas with high renewable energy penetration. By leveraging full electromagnetic transient (EMT) simulations and a new reactive power-voltage sensitivity index, the method effectively balances cost reduction with improved grid resilience during fault conditions.

What Problem Does This Paper Address?

The increasing integration of renewable energy sources and power electronic devices into power grids, coupled with uneven power generation and load distribution, is leading to a higher risk of transient voltage instability, particularly in critical load centers. Traditional methods for addressing this often involve expensive and time-consuming solutions like building new power plants. While synchronous condensers (SCs) are a promising solution for providing much-needed reactive power support and inertia, their effective placement and sizing are crucial due to high installation and relocation costs. Existing configuration methods often rely on simplified steady-state analyses or are computationally intensive, making them less suitable for complex, modern grids. This paper aims to bridge this gap by proposing a more accurate and efficient method for SC configuration that directly considers transient behavior.

Methods

The core of this paper's contribution lies in its proposed configuration method, which is driven by full electromagnetic transient (EMT) simulations. Key steps include:

  • Defining Transient Voltage Stability Indicators: The study introduces and utilizes several indices to quantify voltage stability:
  • Severity Index (SI): Measures the impact of a fault on voltage deviations across multiple buses.
  • Reactive Power-Voltage Sensitivity Index (VSI): Quantifies the effectiveness of injecting reactive power at a specific node on improving voltage stability across the grid. This is a novel index used to guide SC placement.
  • Transient Voltage Instability Risk Index (TVRI): Assesses the magnitude and duration of voltage sags below a threshold.
  • Comprehensive Index (CI): A combined metric to evaluate the overall effectiveness of a configuration, balancing capacity and TVRI.
  • Identifying the Most Severe Fault Scenario: EMT simulations are used to pinpoint the fault scenario that causes the most significant voltage instability.
  • Siting SCs: The VSI index is calculated for all nodes under the most severe fault scenario. The top 10 nodes with the highest VSI values are identified as candidate locations for SC installation.
  • Optimizing SC Capacity: An optimization model is formulated with the objective of minimizing total installed SC capacity while adhering to transient voltage stability constraints. This model is solved using an iterative linear programming algorithm. The VSI is incorporated into the constraints to guide capacity adjustments.
  • Iterative Solution: The process involves repeated EMT simulations and linear programming steps to refine the SC capacity at candidate locations until convergence is achieved.

Datasets

The study utilizes a case study based on the power grid platform in "S Province." The network topology of the load-center region is provided, and specific transmission lines (1-10) are selected for fault analysis. The paper does not introduce new benchmark datasets but rather applies its method to a realistic power grid scenario.

Key Insights and Ideas

  • VSI as a Powerful Siting Tool: The novel Reactive Power-Voltage Sensitivity Index (VSI) proves to be a highly effective heuristic for identifying optimal locations for SCs, directly correlating with their potential to improve voltage stability.
  • EMT Simulation is Crucial for Transient Behavior: Relying solely on steady-state analysis is insufficient for complex grids with high renewable penetration. Full EMT simulations are essential for accurately capturing transient dynamics and ensuring robust SC configuration.
  • Balancing Cost and Performance: The optimization model effectively balances the desire to minimize installation costs (by minimizing total capacity) with the critical need to meet stringent transient voltage stability requirements.
  • Iterative Optimization Efficiency: The proposed iterative linear programming approach, guided by EMT simulation results, demonstrates good convergence and significantly reduces computational burden compared to some existing heuristic methods.
  • Constraint Impact: Stricter voltage constraints lead to improved transient voltage stability (lower TVRI) but require larger SC capacities and thus higher costs. The paper highlights the need for careful selection of these constraints.

Key Results

The proposed method was applied to a case study of the S Province power grid, demonstrating significant improvements in transient voltage stability.

  • Fault Scenario Identification: The N-1 three-phase-to-ground short-circuit fault on transmission line 1 was identified as the most severe scenario, causing the largest SI value.
  • SC Configuration: The optimal configuration involved installing SCs at specific nodes, with Bus 185 and Bus 232 receiving 800 Mvar each, and Bus 51 receiving 344 Mvar.
  • Voltage Stability Improvement:
    • Under the most severe fault (transmission line 1), the overall TVRI was reduced by approximately 66% (from 2.50 to 0.84).
  • For key buses, low transient voltages increased from around 0.635 p.u to 0.916 p.u, and recovery times to 0.8 p.u decreased from ~4.96 s to ~4.33 s.
  • Under a less severe fault (transmission line 2), the overall TVRI was reduced by approximately 51% (from 1.557 to 0.762).
  • Even under a severe external fault, the SC configuration significantly improved voltage recovery, reducing the overall TVRI by 73% (from 5.111 to 1.368).
  • Computational Efficiency: The iterative process converged within a reasonable number of iterations (e.g., 9 iterations for a speed of 0.5), with optimization solving times being very short (<0.2 s) compared to EMT simulation times.

Limitations and Future Work

The authors acknowledge several limitations and suggest avenues for future research:

  • Cost Considerations: The current optimization model primarily focuses on minimizing installed capacity. Future work should incorporate detailed configuration and maintenance costs of SCs, as well as market-driven revenues (e.g., reactive power ancillary services), for a more comprehensive economic analysis.
  • Fault Set Selection: The current fault set selection is based on engineering experience and computational resource constraints. Future research could explore intelligent fault set generation methods using machine learning to automatically identify critical contingencies, balancing computational efficiency with scenario completeness.
  • Dynamic Modeling: The paper suggests that future research should prioritize refining economic analysis through dynamic modeling frameworks that incorporate SC life-cycle costs and market-driven revenues.
  • Generalizability: While the method is demonstrated on a specific grid, further validation on larger and more diverse power systems would be beneficial.

Summary updated

Abstract

The integration of large-scale renewable energy and power electronic devices into the grid, as well as the uneven distribution of power units and loads, further increases the risk of transient instability at critical load centers. The installation of synchronous condensers (SCs) in the grid can enhance its transient stability. Therefore, it is necessary to focus on the siting and sizing of SCs, considering both economic and safety factors. To address this issue, this paper proposes a configuration method based on full electromagnetic transient (EMT) simulation. Initially, relevant indicators for measuring transient voltage stability are defined. Subsequently, the most severe fault scenario was identified through EMT simulation, and the reactive power voltage sensitivity index was generated. Finally, an optimization configuration model is established with the objective of minimizing installation costs and the constraint of ensuring transient voltage stability, and the model is solved using an iterative linear optimization algorithm. The proposed method is applied in a case study of the power grid platform in S Province, and simulation results indicate that it effectively improves transient voltage stability within heavily loaded regions, demonstrating its economic and practical effectiveness.