Testing and Analysis of Vibration Impact on High-Rise Residential Environment

Zhaoshuan Chen, Yufeng Xu, Qilong WangAdvances 2025 · OpenAlex

Abstract

As cities continue to develop and urban buildings increase in number, the issue of environmental vibration affecting urban structures is becoming more prevalent. This article takes as its background the vibration issues arising from the construction of surrounding foundation pit piles for a certain high-rise reinforced concrete residential building. It introduces the testing methods for environmental vibration, presents the results of vibration testing, evaluates these results, and analyzes whether the vibrations generated by the foundation pit pile construction will cause damage or safety issues for residential buildings. The assessment methods in this article can provide valuable references for similar projects.

Introduction

In dense urban environments, new construction projects often occur in immediate proximity to existing high-rise structures. Activities such as pile driving generate significant environmental vibrations that can lead to resident discomfort, interference with sensitive equipment, and potential structural integrity risks. This study examines a specific case where a new foundation pit using prefabricated piles was constructed within a distance of 1.05 to 3.45 meters from an existing 29-story reinforced concrete residential building.

Site layout showing the proximity of existing buildings (10#, 9#, 6#, 5#) to the construction area.

Due to the extreme proximity, residents reported noticeable vibrations, necessitating an objective engineering assessment to distinguish between human perception of vibration and actual mechanical risk to the structure.

Methodology

The research team conducted on-site vibration testing following Chinese national standards (GB50868-2013 and GB 10071-88). The study focused on Building 10#, the structure closest to the pile-driving activity, representing the worst-case scenario for vibration exposure.

Instrumentation and Layout

The monitoring system utilized an INV series intelligent signal acquisition system paired with DASP2006 analysis software. The sensor configuration was designed to capture the building's dynamic response at critical points:

  • Foundation Level: Five measurement points were established to monitor ground-borne vibration entry.
  • Top Floor Level: Four measurement points were placed at the building's peak to monitor structural amplification and sway.
Layout of vibration measurement points on the building floor plan to capture multi-axial data.

Measurements were recorded across three axes: vertical, and two horizontal directions (parallel and perpendicular to the pile construction face). The system was calibrated to capture frequencies between 1 Hz and 100 Hz, extracting peak velocity values for comparison against regulatory safety limits.

Results and Analysis

The empirical data provided a quantitative basis for safety evaluation. The dominant vibration frequency induced by the pile driving was identified as 18.75 Hz at both the foundation and top floor levels.

Safety Evaluation

The measured peak velocities were compared against the permissible limits defined by national building codes for the identified frequency:

  1. Foundation Level: The maximum measured peak velocity was 2.25 mm/s. This is safely below the regulatory limit of 3.66 mm/s for this frequency range.
  2. Top Floor Level: The maximum measured peak velocity reached 4.09 mm/s. While higher than the foundation due to structural amplification, it remained well within the permissible limit of 6.00 mm/s for the upper structure.

Discussion

A key finding of this study is the discrepancy between human perception and structural reality. While the vibrations were significant enough to cause occupant concern, the objective measurements confirmed that the energy levels were insufficient to cause structural damage.

Furthermore, the study validates a proxy assessment approach: by confirming the safety of the most at-risk structure (the closest building), engineers can infer the safety of adjacent structures in the same complex without exhaustive instrumentation of every building. The dual-level monitoring (base and peak) proved essential, as it accounted for the natural dynamic amplification inherent in high-rise reinforced concrete frame-shear wall structures.

Conclusion

The vibration testing and analysis indicate that the foundation pit pile construction posed a low structural safety risk to the existing high-rise building. All measured parameters remained within the safety thresholds established by national standards. This methodology serves as a practical framework for assessing environmental vibration impacts in future urban construction projects.