Abstract
The HPC4AI (High-Performance Computing for Artificial Intelligence) datacenter at the University of Turin’s Computer Science Department was established to meet the rapidly growing computational demands of interdisciplinary AI research. HPC4AI innovates by redefining the traditional roles of Cloud and High-Performance Computing (HPC) systems, where the Cloud provides a modern interface for HPC, and HPC acts as an accelerator for Cloud applications. To date, it has supported over 40 research projects spanning diverse fields such as astronomy, medicine, and human sciences. Additionally, HPC4AI serves as a research and development platform for exploring, developing, and testing novel datacenter technologies. This work outlines the operational management of HPC4AI, highlighting challenges, lessons learned, and key opportunities related to digital twins for datacenters.
Introduction
Modern AI research requires a symbiotic relationship between flexible Cloud services for model inference and user interfaces, and raw High-Performance Computing (HPC) power for intensive training. Managing these hybrid environments is complex, and traditional datacenter management often remains reactive. Researchers at the University of Turin (UniTO) are addressing this by developing a comprehensive Digital Twin (DT) for their HPC4AI facility. The goal is to create a virtual replica that consolidates operational data, simulates thermal and electrical behavior in real-time, and enables proactive, scenario-based optimization.
Methodology
The development of the Digital Twin followed a multi-layered approach, integrating architectural modeling with real-time telemetry.
BIM-to-DT Pipeline
The physical datacenter was first modeled using Building Information Modeling (BIM) via CAD and Revit. This geometric foundation was then imported into the IES Virtual Environment (IES VE) platform for dynamic thermal and energy modeling. This process ensures that the virtual model maintains spatial and semantic accuracy relative to the physical site.
Multi-Source Monitoring
The Digital Twin is fed by three distinct systems: a Building Management System (BMS) for power and cooling, IT monitoring via Pandora FMS for performance metrics, and air quality sensors to track particulates that could lead to hardware corrosion. To handle electrical data sampling intervals, the researchers utilize phasor representation to maintain consistency in steady-state electrical models.
Results and Insights
The integration of BIM with real-time sensor data has yielded significant operational benefits, allowing for a highly detailed view of the facility's state.
Operational Efficiency
The HPC4AI facility achieved a Power Usage Effectiveness (PUE) of 1.1, significantly outperforming the global average of 1.56. This efficiency is supported by a novel two-phase evaporative cooling system designed for high-density GPU servers, capable of dissipating up to 1000W per socket.
Environmental and Acoustic Management
Beyond energy, the study highlights the importance of air quality monitoring to prevent fan clogging. Additionally, the use of triple glazing for the server room's glass walls reduced noise levels by 92 dB, allowing the facility to operate adjacent to departmental offices without disruption. Over four years of operation, the facility experienced only one instance of planned downtime.
Conclusion and Future Work
While the foundational geometric and thermal models are validated, the project is currently in its initial phase. Future efforts will focus on moving from human-in-the-loop monitoring to AI-driven automated decision-making for adaptive cooling and predictive maintenance. By forecasting hardware failures based on thermal or electrical signatures, the Digital Twin will further enhance the resilience and sustainability of the HPC4AI infrastructure.
Summary updated