Characteristic spectrum analysis on joint detection of PD in switchgear
Abstract
With the deficiency of discharge spectrum analysis and combined use of means of PD detection for switchgear, this paper has set up four kinds of PD model of switchgear according to four kinds of typical PD (corona discharge, surface discharge, internal discharge and floating potential discharge). Moreover, based on homemade PD detection system of switchgear, methods including TEV, AE and UHF are used for feature extraction of typical PD model and comparative analysis of discharge spectrum. Furthermore, multi-dimension maintenance strategy based on PD detection of switchgear is proposed.
BibTeX
@inproceedings{jia2015characteristic,
author = {Fan JIA},
title = {{Characteristic spectrum analysis on joint detection of PD in switchgear}},
booktitle = {Openalex Unknown},
year = {2015},
doi = {10.1201/b18409-13},
}Ask Althea to put this paper to the test.